Installation
2–14
975-0466-01-01
Mounting on Poles or Rails
To mount the unit using poles:
1. Ensure that poles or rails are securely assembled in place. If using horizontal
rails, two rails are required: one for the mounting bracket and another for
securing the bottom edge of the inverter (see Figure 2-6).
2. Connect the mounting bracket vertically to the pole or rail:
•
Be sure to use at least two bolts to secure the bracket to the support.
•
Position the lower edge of the bracket a minimum of 130 cm above the
floor or ground.
•
Position the top edge of the bracket a minimum of 34 cm below any
ceiling or roof.
3. If using a single vertical pole, ensure that the inverter is secure and unable to
rotate around the pole.
Figure 2-6
Examples of Mounting on a Pole or Rails
Mounting bracket
130 cm
100 cm
At least 2 bolts to
secure bracket to
poles/rails.
46 cm
For securing
the bottom of
the inverter
Ground/Floor
34 cm