Installation
2–12
975-0466-01-01
Installing the Mounting Bracket
The mounting bracket for the GT Inverter allows the unit to be easily mounted and
removed for servicing. It has one hook that matches a corresponding hook on the
back side of the inverter.
Clearance Requirements
For optimal and safe operation, make sure there is adequate clearance around the
inverter. If clearances are less than these recommendations are used, additional
power reduction may occur at high ambient temperatures.
Figure 2-5
Mounting Bracket and GT Inverter
238 mm
183 mm
Mounting slots for securing the inverter
Mounting flanges
Rectangular slots × 8:
8 mm × 30 mm
Table 2-3
Inverter Clearance Requirements
Location
Minimum Clearance
Above
30 cm
Below:
•
Inverter
•
Bracket
Outdoors:
•
100 cm
•
130 cm
Indoors: the same clearances are recommended but not required.
In front
Sufficient room to allow for easy access to read the display and to prevent
accidental contact with hot surface.
On sides
Units can be mounted side by side with no clearance between them, but
15 cm of clearance around the outermost two units is recommended. In hot
climates, some clearance between units may be needed to prevent thermal
derating.
Summary of Contents for GT2.8-AU-QC-230
Page 1: ...Xantrex Grid Tie Solar Inverter Owner s Manual GT2 8 AU QC 230 GT5 0 AU QC 230 ...
Page 2: ......
Page 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Page 8: ...vi ...
Page 14: ...Contents xii 975 0466 01 01 ...
Page 16: ...xiv ...
Page 18: ...xvi ...
Page 58: ...4 4 ...
Page 70: ...Monitoring the Inverter 5 12 975 0466 01 01 ...
Page 76: ...Maintenance and Troubleshooting 6 6 975 0466 01 01 ...
Page 82: ...A 6 ...
Page 89: ......