Operation
Power Supply Operation
Release 2.1
55
User Settings
(Save and
Recall)
If you have a frequent or constant need for a specific voltage and current output, you
can save these setpoints in the power supply’s memory as a user setting. Once a
setting is stored, it remains in the power supply’s memory after the unit is powered
off.
Ten user setting memory locations are available, and each saves the following
parameters:
•
Voltage setpoint
•
Current setpoint
•
Over-voltage protection setpoint (OVP)
•
Under-voltage protection setpoint and shutdown configuration (UVP)
•
Over-current protection setpoint and shutdown configuration (OCP)
•
Under-current protection setpoint and shutdown configuration (UCP)
•
Foldback protection mode and delay settings
•
AC Off auto recovery configuration (ACO)
•
OTP auto-recovery configuration
•
Aux line configuration
•
Voltage and current soft limits
•
Triggered setpoints and trigger source
To store (save) settings:
*SAV <user-setting>
or the SCPI equivalent for multichannel addressed units
SYST<channel>:SAVE <user-setting>
where <user-setting> is an integer from 1 to 10.
Example:
*SAV 1
will save all the present settings to user setting location 1.
To recall settings:
*RCL <user-setting>
To save default settings:
*SDS <user-setting>
Note
All parameters are saved and used when the user setting is recalled. Therefore, you
should set parameters that you do not care about to the factory defaults.
Summary of Contents for GPIB-M-HPD
Page 2: ......
Page 18: ...List of Figures xvi Operating Manual for Multichannel Functionality GPIB M...
Page 94: ...Current Sharing Operation 92 Operating Manual for Multichannel Functionality GPIB M...
Page 98: ...GPIB Performance Specifications 96 Operating Manual for Multichannel Functionality GPIB M...
Page 118: ...SCPI Command Reference Expressions 116 Operating Manual for Multichannel Functionality GPIB M...
Page 133: ......