Original Operating Instructions
BATI0XXX-ES-1-ZZZ-1
Installation
O_BATI_0XXX-ES-1-ZZZ-1_V1.4_GB
Seite
33
von
60
3.4.3 Supply Voltage
The product is operated with a supply voltage of 230 V/TN-grid.
Requirements:
•
Supply lines must be connected and secured by means of a 16 A miniature
circuit breaker with a tripping characteristic B or a 16 A fuse with a tripping
characteristic gG.
Depending on the demand the connection can be done in two ways:
Variant 1:
Buffered supply voltage for control and unbuffered supply voltage for fan
and heating
Procedure:
1.
Remove
the sliding ground plate.
2.
Remove
bridges:
(
–X9.1)
(
–X9.2)
(
–X9.3)
(
–X9.4)
3.
Connect
PE, L and N conductor of the
unbuffered supply voltage
to
terminal strip (
–X9):
PE conductor
(
–X9.5)
L conductor
(
–X9.1)
N conductor
(
–X9.3)
4.
Connect
PE, L and N conductor of the
buffered supply voltage
to terminal
strip (
–X9):
PE conductor
(
–X9.5)
L conductor
(
–X9.2)
N conductor
(
–X9.4)
Figure 14: Connection supply voltage