11.2
Technical Data
11.2.1 Electrical Data
Table 10: Electrical data
BATx0280-ES-1-400-1
(Outdoor)
Remarks
AC SIDE
Maximum rated apparent
power
280 kVA
At rated AC voltage
Rated active power
280 kW
At (cos
(φ)) = 1.0
Rated AC voltage
400 V, 3~ + neutral, 50 Hz
Other values on request
Grid configuration
TN
Maximum output current
404 A
Maximum short-circuit
current
36 kA
Line power factor (cos φ)
> 0.98
At > 20 % of rated power
AC-current distortion (THD)
< 3 %
DC SIDE
Nominal voltage
750 V
Voltage range
450 … 890 V
Currents
± 630 A
Maximum short-circuit
current
40 kA
Current THD
< 3%
Number of DC Inputs
1
GENERAL
Control strategy
CC-CV
Power controlled
Island mode
Efficiency
(92.2|97.1|97.2|96.8|96.4)
%
At (10|30|50|75|100) %
power
Loss in standby (at night)
< 30 W
Maximum auxiliary power
< 600 W
+ Heating requirements
MEASURING ACCURACY
Grid frequency
± 40 mHz
Average value of 8 grid
periods
Summary of Contents for BAT 0280-ES-1-400-1 Series