Original Operating Instructions
BATx0280-ES-1-400-1 (Outdoor)
Installation
O_BATx0280-ES-1-400-1_(Outdoor)_V1.3_GB
Page
43
of
69
3.5.2.7 External Temperature Measurement Device
Required material (not include in scope of delivery):
•
Temperature sensor (e.g. Pt100)
Figure 20: Cable routing terminal strip (-X17)
Procedure:
1.
Locate
the terminal strip (-X17) (Figure 20).
2.
Open
the corresponding cable ducts.
3.
Route
the cable through the cable entry grommet.
4.
Connect
the lines to the terminals (-X17.3) and (-X17.4).
5.
Close
cable ducts.
6.
Fix
the cable with a cable clamp.
3.6
After Installation
After installation the following items must be checked:
•
No waste packaging, waste and tools within the product
•
No transportation and installation damages occurred.
•
Connection lines and terminals are properly connected and the torque has been
checked.
•
If any of the foregoing is not ensured, the product may be damaged. The
manufacturer disclaims any and all liability for damages resulting from a failure
to following the listed steps in this Section 3.6.