Rectifying faults
Error EA
EA
and
flashing.
During operation: flame not detected
Check
Action
1.
Is a burner flame visible?
yes:
↓
5.
no:
↓
2.
2.
Is the gas cock turned on?
yes:
↓
3.
no:
B
Open the gas cock.
B
Press
, restart the appliance.
EA?
↓
3.
3.
Is there air in the supply pipe?
yes:
B
Vent supply pipe.
B
Press
, restart the appliance.
EA?
↓
4.
no:
↓
4.
4.
Natural gas models:
does the building have a supply pressure
regulator?
yes:
B
Check that it is fitted correctly and functioning prop-
erly and correct if necessary.
B
Check supply pressure, inform gas company if outside
correct range.
B
Is correct code plug fitted?
B
Press
, restart the appliance.
EA?
↓
5.
no:
↓
5.
LPG models:
is the flow rate of the gas supply to the
appliance correct?
yes:
↓
5.
no:
B
Is there enough gas in the supply cylinder?
B
Is there air in the supply pipe?
B
Is the solenoid valve in the "meter cabinet” opening?
B
Is the supply pressure OK? (if the supply pressure is
too high, check the pressure regulator in the “meter
cabinet” and on the LPG supply cylinder)
B
Press
, restart the appliance.
EA?
↓
5.
5.
Is the earth connection correct?
yes:
↓
6.
no:
B
Correct the electrical connection.
B
Press
, restart the appliance.
EA?
↓
6.
6.
Is the condensation trap blocked?
yes:
B
Clean out condensation trap discharge pipe.
B
Press
, restart the appliance.
EA?
↓
11.
no:
↓
7.