Rectifying faults
Error Fd
Flue gas levels incorrect, CO level too high
Check
Action
1.
Does the gas supply type match the
specifications on the appliance iden-
tification plate?
yes:
↓
2.
no:
B
Convert appliance to correct gas type.
Flue gas levels incorrect? 2.
2.
B
Test gas supply pressure - OK?
Does pressure match figure speci-
fied in installation instructions?
yes:
↓
3.
no:
B
Decommission appliance.
Bei Erdgas:
B
Notify gas company.
b
3.
Problem with flue?
B
Check CO
2
level in combustion
air.
Is CO
2
level above 0,2 % ?
yes:
B
Check flue and repair or replace if necessary.
Flue gas levels incorrect? 4.
no:
↓
4.
4.
Flue gas CO
2
levels measured at
min. and max. load do not match
specified levels?
B
Measure CO
2
levels.
yes:
B
Adjust CO
2
level as per installation instructions.
Flue gas levels incorrect? 5.
no:
↓
5.
5.
Gas volumetric flow too high when
CO
2
level correctly set.
yes:
B
Reduce gas volumetric flow rate by means of
adjusting screw on gas valve and/or gas flow
restrictor.
B
Check CO
2
adjustment.
Flue gas levels incorrect? 6.
no:
↓
6.
6.
B
Power OFF the appliance.
B
Turn off gas cock.
B
Change the gas valve.
B
Open the gas cock.
B
Turn ON the appliance.
B
Check appliance for leaks.