40
Repair or replace
faulty sensor or
wiring to it.
FAIL POINT G
No
Yes
No
Replace faulty sensor.
Remove 20 - way
connector from control
board. Is the resistance
across contact pairs 15/16
(pink wires), 17/18 (red
wires) and 19/20 (yellw
wires) between 1kohm and
30 kohm respectively
when boiler is cool?
Note: Take care not to
damage contacts.
Repair cables /
connectors or
replace main
harness.
Visually inspect all three
temperature sensors on
the appliance (combustion
chamber cover needs to be
removed to see the central
heating / primary sensor).
Are they electrically
connected and look o.k. ?
Is there continuity
from the contacts to
the faulty sensor?
Yes
No
Yes
Replace control board.
FA
IL POINT H (Primary Ov
erhea
t)
No
Yes
No
Rectify fault.
Is the boiler fully
water pressurised
and is all air vented?
Replace control
board.
No
Is there 230Vac at
connector X5 pin 1?
At this point it is difficult to accurately
diagnose the fault. Probable causes are:
1. Primary sensor out of tolerance.
2. Faulty gas to water heat exchanger.
3. Scaled/inefficient water to water heat
exchanger.
4. Faulty control board.
5. Faulty primary overheat thermostat (or
cables to it).
Yes
Reset the controls
and restart the boiler.
Does the pump run?
Inspect pump cable.
If o.k. repair or
replace pump.
Yes
Remove combustion
chamber cover. Is
primary / central
heating sensor
correctly fitted to the
heat exchanger?
Yes
No
Refix sensor.