
1.1
Gas Safety (Installation and Use) Regulations 1998: All gas
appliances must be installed by a competent person in
accordance with the above regulations. Failure to install
appliances correctly could lead to prosecution.
1.2
The manufacturers notes must not be taken, in any way, as
overriding statutory obligations.
1.3
The compliance with a British Standard does not, of itself,
confer immunity from legal obligations. In particular the
installation of this appliance must be in accordance with the
relevant requirements of the following: Gas Safety (Installation
and Use) Regulations 1998, current IEE Wiring Regulations, local
Building Regulations, Building Standards (Scotland)
(Consolidation), byelaws of the local Water Company and Health
and Safety Document No. 635 (Electricity at Work Regulations
1989). It should be in accordance with the relevant
recommendations of the following British Standards:
BS 6798: Specification for Installation of gas fired hot water
boilers of rated input not exceeding 60 kW (Gross)
BS 5449: Central Heating for Domestic Premises
BS 5546: Installation of gas hot water supplies for domestic purposes.
BS 5440:1: Flues and Ventilation for gas appliances of rated input
not exceeding 60kW (Gross): Flues.
BS 5440:2: Flues and ventilation for gas appliances of rated input
not exceeding 60kW (Gross): Air Supply.
BS 6891: Installation of low pressure gas pipework installations
up to 28mm (R1).
BS 6700: Domestic Water Supply in Buildings.
BS 7593: Water Treatment in domestic heating systems.
1.4
To ensure that the installation will perform to the highest
standards, the system and components should conform to any
other relevant British Standards in addition to those mentioned
in the instructions.
1.5
In accordance with the requirements of COSSH the appliance
does not contain any substances which are harmful to health.
1.6
Product Liability regulations indicate that, in certain
circumstances, the installer can be held responsible, not only for
mistakes on his part but also for damage resulting from the use of
faulty materials. We advise that, to avoid any risk, only quality
approved branded fittings are used.
1.7
The advice and instructions given in this document covers, as
far as possible, the foreseeable situations which may arise. Contact
Worcester Heat Systems Technical Department, Telephone: 08705
266241, for advice on specific installations.
2.1. GENERAL INFORMATION
2.1.1
The appliance is set to provide the maximum output of
24kW to the domestic hot water and to the central heating .
2.1.2.
The domestic water section of the appliance is suitable for
mains water pressures of up to 10bar.
2.2 ELECTRICAL SUPPLY
Mains supply: 230V ~ 50 Hz. 95 Watts.
External fuse: 3A. Internal fuses: T 2A (F1), and T 1A (F2).
2.3 GAS SUPPLY.
Check the data plate (located on the inner cover of the appliance)
to ensure the appliance has been set up for the correct gas
supply. The boiler requires a gas flow of 2.9 m
3
/h of natural gas
(G20).
The meter governor or regulator should deliver a dynamic
pressure of 20mbar for natural gas at the appliance, which is
about 18.5mb at the gas valve inlet pressure test point.
The complete installation, including the gas meter (G20), must be
tested for soundness and purged. Refer to BS 6891.
2.4 PACKING
The appliance and flue components are packed in separate
cartons.
2.5 INSTALLATION.
The appliance is suitable for indoor installation only.
The appliance is supplied for connection to a sealed system but
is suitable for use with an open vent system.
Any specified ventilation openings made into a wall or
compartment door must not be obstructed.
If the appliance is to be fitted into a compartment then the
compartment must conform to the requirements of BS
6798:1987: Section 6.
The clearances specified for installation and servicing must be
maintained.
A water filter, flow turbine and regulator, nominal flow 18 l/min.
to supply water at an average temperature rise of 40°C, are
fitted to the mains cold water inlet on the appliance.
A heatbank of 60 litres of circulating primary water with a
diverter valve to direct the primary water to the heat store or to
the central heating system system is contained within the
casing.
NOTE: As the dry weight of the appliance is 96kg, more than
one person will be required when moving the appliance.
2. General Information
1. Installation Requirements
2
10.
Electrical .................................................................... Page 12
11.
Installing the Appliance ............................................ Page 13
12.
Commissioning the Appliance ................................ Page 18
13.
Instructions to the User ............................................ Page 20
14.
Inspection and Service .............................................. Page 20
15.
Replacement of Parts ................................................ Page 21
16.
Operational Flow Diagrams ...................................... Page 34
17.
Fault Finding .............................................................. Page 36
18.
Component Parts List ................................................ Page 42
1.
Installation Requirements ........................................ Page 2
2.
General Information .................................................. Page 2
3.
Technical Data ............................................................ Page 5
4.
Siting the Appliance .................................................. Page 8
5.
Flue Terminal Position ................................................ Page 8
6.
Air Supply .................................................................... Page 9
7a. Sealed System ............................................................ Page 9
7b. Open Vent System ..................................................
Page 10
8.
Open Vent System ...................................................... Page 10
9. Gas Supply .................................................................. Page 11
Contents
Summary of Contents for Highflow 400 BF
Page 43: ...43 ...