18
Fig. 21. Gas control valve adjustment.
1
1.
Gas valve.
2.
Outlet union.
3.
O-ring.
4.
Pilot gas pipe.
5.
Burner pressure test point.
6.
Gas valve solenoid connection.
7.
Gas valve solenoid connection.
8.
Burner pressure adjustment.
9. Spark electrode earth.
10. Spark electrode lead.
11. Gas valve connector and fixing screw.
2
3
4
5
6
7
8
9
10
11
1
2
3
4
1.
Modulator connections -
polarity not important.
2.
Minimum burner pressure.
3.
Maximum burner pressure.
4.
Burner pressure test point.
NOTE:
Remove the adjustment cover.
Benchmark Water Treatment: For optimum performance after
installation, this boiler and its associated central heating
system should be flushed in accordance with the guidelines
given in BS7593:1992 - Treatment of water in domestic hot
water systems. Full instructions are supplied with proprietary
cleansers sold for this purpose. If an inhibitor is to be used
after flushing, it should be used in accordance with the
inhibitor manufacturers instructions.
Suitable flushing agents and inhibitors are available from Betz
Dearborn Tel: 0151 4245351 and Fernox Tel: 01799 521133.
Instructions for use are supplied with these products.
IMPORTANT:
Any system cleanser must be fully flushed from the
system before any inhibitor is added.
12.1 SUMMARY
The appliance is dispatched with the controls set to provide a
maximum output for domestic hot water and central heating
load of 24 kW.
The appliance automatically modulates to satisfy lower heat loads.
Domestic Hot Water Circuit
Confirm that the mains water supply has been flushed out at
installation. If not it will be necessary to disconnect the cold
water inlet pipe from the appliance and thoroughly flush.
Central Heating System
Flush the system before starting to commission the appliance
and, at the end of the commissioning procedure, drain whilst
hot. Immediately refill and re-pressurise adding an inhibitor as
necessary.
Gas Service.
The complete system, including the meter, must be inspected and
tested for soundness and purged as indicated in BS 6891. In the
event of a leak, or suspected leak, at the ‘O’ ring joint on the main
appliance manifold, connect a manometer to the test point on the
inlet of the multifunctional gas valve. A soundness test carried out
after turning off the appliance gas cock will test the section
between the gas cock and the gas valve, thus enabling the leak to
be traced to the ‘O’ ring.
12.2 APPLIANCE AND CENTRAL HEATING SYSTEM
PREPARATION.
12.2.1 VENT THE APPLIANCE.
Remove the cabinet front panel before starting the
commissioning procedure. See Fig. 14.
12. Commissioning The Appliance
Fig. 20.
Pilot burner assembly.
1.
Pilot assembly
2.
Pilot head
3.
Pilot assembly fixing screws (2)
4.
Pilot gas pipe fixing nut
5. Pilot gas pipe
6. Spark electrode (secured by clip)
7. Flame sense electrode
8. Flame sense electrode fixing nut
9. Spark electrode earth lead
2
3
6
4
5
Pilot flame length 18-20mm
7
8
1
9
Summary of Contents for Highflow 400 BF
Page 43: ...43 ...