36
OFF
OFF
OFF
No lights and no functions
A
OFF
No green light. All functions o.k and red lights o.k.
B
ON
OFF
No CH light and no CH function. HW function o.k.
C
ON
OFF
No HW light and no HW function. CH function o.k.
D
ON
Serious temperature fault in CH or HW mode.
E
ON
SLOW FLASH
Ignition sequence failure lockout. Pilot gas not detected after 2 minutes
F
(reset using CH temperature control).
ON
FAST FLASH
Sensor failure.
G
ON
SLOW FLASH SLOW FLASH
Safety Temperature Limiter lockout (reset using CH temperature control).
H
ON
ALTERNATE FLASH
Tank overheat lockout (call Service Engineer).
I
ON
FAST FLASH
FAST FLASH
Diverter spillage trip (OF only)
J
Other faults
K
17. Fault Finding
GREEN
LIGHT
RED CH
LIGHT
RED HW
LIGHT
FAILURE DESCRIPTION
Light Situation During Fault
CH LIGHT
(Red)
HW LIGHT
(Red)
POWER LIGHT
(Green)
CH CONTROL
HW CONTROL
FAIL
POINT
SLOW FLASH
is once per second
FAST FLASH
is five times per second
NOTE: There is no mains supply isolating switch on the appliance
Note:
This fault-finding information is for guidance only. Worcester Heat Systems cannot be held responsible for costs incurred by
persons not deemed to be competent.
The electronic control system for this boiler incorporates three lights on the facia. These are used to show normal operating status. But as
a secondary function, by flashing, they can also be used to help provide fault diagnostics. Therefore, with individual or groups of lights
being permanently off, on or flashing, every normal fault can be identified.
To use the fault finding system, select a box below which represents the light situation during your fault. Then refer to the appropriate fail
point. This fault-finding system assumes that the appliance has been operating correctly until the time of failure and not an installation
error..
PRELIMINARY CHECKS
Preliminary electrical system checks are the first electrical checks to be carried out during a fault-finding procedure. On completion of
the Service/Fault-Finding task which has required the breaking and remaking of electrical connections, check (a) EARTH CONTINUITY,
(b) SHORT CIRCUIT CHECK, (c) POLARITY and (d) RESISTANCE TO EARTH.