6 720 610 597 GB (03.02)
18
Installation
3.9.1
Siting the Flue Terminal
The flue must be installed in accordance with
BS 5440:1 and the Building Regulations. Flue termi-
nals in carports and under balconies are to be avoided.
The terminal must be positioned so that it does not
cause an obstruction nor the combustion products a
nuisance. See fig. 15 and table 9.
The terminal will, at times, give out a plume of water
vapour and consideration must be given to this when
choosing a terminal position. Keep clear of security
lighting, activated by passive infra-red sensing heads.
If the terminal is less than 2 m above a surface to which
people have access then a guard must be fitted. The
guard must be evenly spaced about the terminal with a
space of 50 mm in each direction and fixed with plated
screws.
A guard Type K6 for the standard horizontal flue, can be
obtained from Tower Flue Components, Vale Rise, Ton-
bridge TN9 1TB.
Fig. 15
Minimum dimensions of flue terminal positions (all types) (see fig. 15)
Dimension
Terminal Position (kW input expressed in net)
Balanced flues room sealed: Fanned draught
A
1)
Directly below an opening, air brick, opening windows, etc.
300 mm
B
1)
Above an opening, air brick, opening window, etc.
300 mm
C
1)
Horizontally to an opening, air brick, opening window, etc.
300 mm
D
Below gutters, soil pipes or drain pipes
75 mm
E
Below eaves
200 mm
F
2)
Below balconies or car port roof (lowest point)
200 mm
G
From a vertical drain pipe or soil pipe
150 mm
H
From an internal or external corner
300 mm
I
Above ground roof or balcony level
300 mm
J
From a surface facing the terminal
600 mm
K
From a terminal facing the terminal
1200 mm
L
From an opening in the car port (e. g. door, window) into the dwelling
1200 mm
M
Vertically from a terminal on the same wall
1500 mm
N
Horizontally from a terminal on the same wall
300 mm
O
From the wall on which the terminal is mounted
Not applicable
P
From a vertical structure on the roof
Not applicable
Q
Above intersection with roof
Not applicable
Table 9
1)
In addition, the terminal should not be nearer than 150 mm (fanned draught) to an opening in the building fabric formed for the purpose of accommo-
dating a built-in element such as a window frame.
2)
Not recommended.
Summary of Contents for GREENSTAR HE combi Series
Page 174: ...7 181 465 347 01 07 50 Appendix...
Page 175: ...7 181 465 347 01 07 Appendix 51...
Page 176: ...Appendix...