Maintenance
9.3.14 Flow switch
B
Shut the mains water inlet valve and drain the domes-
tic hot water circuit.
B
Pull-off the connectors from the micro-switch.
B
Unscrew the inlet and union connection and remove
the assembly.
B
Reset the domestic hot water flow rate on the new
assembly.
Fig. 61
9.3.15 Primary Heat Exchanger
B
Drain the appliance.
B
Check that the gas supply is turned off.
B
Check that the appliance is electrically isolated.
B
Remove the fan assembly complete with the gas/air
tube and mixer assembly. Refer to section 9.3.2.
B
Remove the burner. Refer to section 9.2.
B
Disconnect the sensors. Refer to section 9.3.6.
B
Undo the central heating flow union.
B
Undo the top connection of the pump. Refer to
fig. 57.
B
Undo the grey plastic cap, next to the top pump con-
nection at the base of the heat exchanger.
B
Unscrew and remove the condensate trap. Refer to
section 9.2.
B
Unscrew and remove the two screws securing the
heat exchanger top bracket to the rear panel.
B
Lift up the flue duct, item 271, refer to fig. 2.
B
Pull forward from the top and lift the heat exchanger
from the casing.
B
Transfer components, as necessary, to the new heat
exchanger.
B
Ensure that all the seals are in place and all of the
connections are tight before re-commissioning the
appliance.