7 181 465 347 (01.07)
22
Rectifying faults
b1
flashing.
Code plug not detected.
Check
Action
1.
No fault or fault code
FC
displayed
on text display?
yes:
B
Power OFF the appliance.
B
Fit code plug (correctly), making sure code
number (see Appendix) is correct.
B
Turn ON the appliance.
b1?
↓
no:
↓
2.
B
Activate menu option
Show serv-
ice parameters
.
B
Select
1.2 Code plug
.
B
Compare number displayed with
that shown in Appendix.
No number or incorrect number
(last three digits) displayed.
yes:
↓
no:
↓
3.
Code plug loose, incorrect or defec-
tive.
B
Power OFF the appliance.
B
Replace code plug
1)
, making sure code number
is correct.
B
Turn ON the appliance.
b1?
↓
1)
For order no., refer to Appendix
4.
The PCB control board is damaged.
B
Power OFF the appliance.
B
Disconnect the boiler electrical connection.
B
Change PCB control board.
B
Reconnect the boiler electrical connection.
B
Turn ON the appliance.