35
Light indication
during fault not
covered by
above details.
Control board is likely
to be wet or damaged
or malfunctioning.
Check for wet board or
connections. Dry and
re-use or replace
control board. (Section
16.4.23).
FAIL POINT K
Hot water
temperature always
too hot during a
demand (not
regulating).
Hot water sensor
could be off or poorly
fixed to pipe.
Repair or replace
sensor.
(Section 16.4.11).
Water temperature
very low/low gas
pressure (with all
knobs set to
maximum)?
Remove multiway
connector from board
position
ST16
. Is the
resistance across
contacts 1 and 2
(blue wires) below
60 ohms.
Remove blue (top)
connector from gas
valve.
Is there continuity
along blue wires to
multiway connector?
Is the gas set to correct
pressure?
Set pressure.
No
No
Repair wires or replace
harness.
No
Yes
Yes
Replace gas valve.
(Section 16.4.9).
Replace control board.
(Section 16.4.23).
Yes
Inspect the small
resistor that is
attached to the
multiway connector.
Is it missing or loose
or in poor condition?
Replace control board.
(Section 15.4.20).
Replace mains
harness.
FAIL POINT J “Internal F
ault”
No
Yes
Replace control board.
(Section 16.4.23).