Manual 26727
VariStroke-I (VS-I) Electro-hydraulic Actuator
Woodward
81
Configure Alarms/Shutdowns Page
Figure 6-6. Alarms and Shutdowns Configuration Screen
From the Alarm/Shutdown Configuration page, some of the alarms and shut downs can be configured.
Editable faults are shown as colored buttons on the page. The colored buttons can be configured based
on the following descriptions:
Changing these settings may cause the actuator to move and/or shut
down. Ensure all personnel are clear of moving components before
changing values.
If an active Alarm is toggled to a Shutdown, the
actuator will immediately shut down. It is recommended that the
alarm be disabled before configuring it and then re-enabled when
configuration is completed.
Enable/Disable (E/D):
Enables or disables the alarm/shut down.
Note:
Even if an active alarm/shut down is disabled, shows as active on the Alarms/Shutdowns
page; however, it will have no effect on the general Alarm or Shutdown indications.
Alarm/Shutdown (A/S)
: Determines the action that will take place when the alarm is active and enabled.
Latching/Non-Latching (N/L)
: When set to Latching, a triggered alarm will remain active until the driver
is reset. When set to Non-Latching, a triggered alarm will de-activate once the problem is remedied.
Released