Manual 26727
VariStroke-I (VS-I) Electro-hydraulic Actuator
Woodward
41
Figure 3-5. Incorrect Lifting Method
The VS-I Actuator is designed for support by the hydraulic power
cylinder mating surface. Additional supports are neither needed nor
recommended.
The servo valve is not designed to carry any load resulting from field
mounting. For VS-I Integrated, the user is obligated to maintain the
minimum required gap between servo valve and the actuator
installation surface. For reference see outline drawing (Figure 3-1).
Any mounting deviation from the one recommended by Woodward
might cause assembly damage, improper performance or operator
injury risk.
Improper mounting might be considered as a violation of warranty
conditions.
Maximum allowable linkage misalignment is 5°. It is highly
recommended that the customer strictly warn the installer of this.
Assure required pattern tolerance is adhered to based on interface as
shown in Figures 3-1 and 3-2.
Released