Balanced flue system
Design information
Versions as condensing boilers up to 24 kW
Maximum length
1) 2)
[m]
DN60/100 DN80/125
B23
Flue inside a duct and combustion air directly through the boiler (open flue) + 2 m horizontal
connecting line
-
30
B33
Flue DN 80 inside a duct + 2 m horizontal concentric connection line (open flue)
13
30
B33
Connection to a moisture-resistant flue gas chimney with horizontal concentric connection
pipe (open flue)
Calculation to
DIN EN 13384
(MRC manufacturer)
C13x Horizontal roof outlet through a pitched roof,
not for CGB-11 with DN 60/100
(balanced flue
- on-site dormer)
9
10
C13x External wall outlet (balanced flue) (for DE < 11 kW)
5
10
C33x Vertical concentric roof outlet through a pitched or flat roof,
vertical concentric balanced flue for installation in a duct (balanced flue)
9
22
C43x Connection to a moisture-resistant balanced flue chimney (MRC) maximum pipe length from
the centre of the boiler bend to the connector 2 m (balanced flue)
Calculation to
DIN EN 13384
(MRC manufacturer)
C53
Connection to the flue in a duct and ventilation air supply through the external wall
-
30
C53x Connection to a flue on an external wall (balanced flue)
-
22
C83x Connection to a flue in a duct and ventilation air supply through an external wall (balanced
flue)
-
30
C83x Concentric connection to a moisture-resistant flue gas chimney and combustion air through
an outside wall (balanced flue)
Calculation to
DIN EN 13384
(MRC manufacturer)
C93x Vertical flue for duct installation DN 80
rigid/flexible
+ 2 m horizontal concentric connecting
line
13
22
1)
Available fan draught: 90 Pa
(The maximum length corresponds to the total length from the appliance to the flue terminal)
Note: Systems C33x and C83x are also suitable for ins
-
tallation in garages.
Where necessary, adapt the installation examples to the
relevant Building Regulations and requirements of your
country/region. Discuss any questions relating to the
installation, particularly of inspection pieces and ventilati-
on apertures (ventilation generally required above 50 kW
output) prior to installation with your local heating engineer/
flue gas inspector.
The length dimensions refer to concentric balanced flue
and flues, specifically only to original Wolf components.
Balanced flue systems DN60/100 and DN80/125 are
certified as systems together with Wolf gas condensing
boilers.
The following balanced flue or flues with CE-0036-
CPD-9169003 certification may be used:
- Flue DN80
- Concentric balanced flue DN60/100 and DN80/125
- Flue DN110
- Concentric balanced flue (on an external wall) DN80/125
- Flue, flexible DN83
The necessary type plates are supplied with the respective
WOLF accessory.
Observe all additional installation instructions included with
accessories.