26
3061344_201509
Checking the gas supply pressure
Checking the gas supply pressure
Work on gas components MUST ONLY be pre
-
formed by a registered gas fitter. Work which is
carried out incorrectly may lead to gas escaping,
resulting in a risk of explosion, asphyxiation or
poisoning.
• Switch OFF the gas fired boiler. Open the gas shut-off val-
ve.
• Pivot the control unit lid down.
Unlock the casing lid with the l.h. and r.h. rotating locks.
Release the lower part of the casing lid and unhook at the
top.
• To pivot the control unit, push in the tab on the r.h. side of
the thermomanometer using a screwdriver.
• Pivot the control unit out.
• Release the plug at test nipple
and vent the gas supply
pipe.
• Connect the differential pressure meter to „+“ at test port
.
Connect „-“ against atmosphere
• Switch ON the ON/OFF switch.
• After starting the boiler, check the supply pressure at the
differential pressure gauge.
Fig.: Check the gas supply pressure
Natural gas:
If the supply pressure lies outside the 18 to 25
mbar range, adjustments must not be carried
out and the boiler must not be taken into use.
NB
LPG:
If the supply pressure lies outside the 25 to 45
mbar range, adjustments must not be carried
out and the boiler must not be taken into use.
NB
Fig.: Push in the tab
Tab
Fig.: Open the rotating locks
rotating lock