6
3061344_201509
Control unit / Function / Operation
DHW temperature selector
When gas fired condensing boilers are combined with a DHW cylinder, setting 1 - 9
corresponds to a cylinder temperature of 15 - 65 °C. The setting on the DHW thermo-
stat becomes ineffective when the system is used in conjunction with a digital room
thermostat or a weather-compensated controller. The temperature will then be selected
at the controller (accessories). With combi boilers, setting 1 - 9 corresponds to a DHW
temperature of 40 - 60 °C.
Heating water temperature selector
The factory setting range 2 - 8 corresponds to a heating water temperature of 20 - 75 °C.
The setting on the heating water thermostat becomes ineffective when the system is used
in conjunction with a digital room thermostat or a weather-compensated controller.
ON/OFF switch
The gas fired boiler is OFF in position 0.
Reset
A fault is reset by pressing the reset button which will also restart the system. Pressing
the reset button reactivates the system, if there was no fault.
Illuminated ring as status indicator
0
I
9
1
2
8
3
7
4
6
5
2
8
3
7
4
6
5
Display
Explanation
Flashing green
Standby (power supply ON, no heat demand)
Constant green
Heat demand: pump running, burner OFF
Flashing yellow
Emissions test mode
Constant yellow
Burner ON, flame steady
Flashing red
Fault