78
3064298_201507
31. Contractor level
The IDU service allows you to call up the process values for the indoor module.
31.6 IDU service
Main menu
Submenu
Menu item
Chapter
Password for contractor level
Contractor
← back
Special
IDU service
ODU service
Fault history
Delete fault history
IDU service
T_boiler
T_return
T_outside
T_header
T_DHW
HC pressure
°C
°C
°C
°C
°C
°C
If a parameter reset is carried out, all settings and statistical data are reset to factory
settings. See Parameter settings
31.4 Parameter reset
Main menu
Submenu
Menu item
Chapter
Password for contractor level
No
Yes
Reset
parameters to
factory settings?
No
Yes
Reset
parameters to
factory settings?
Contractor
←
back
Relay test
System
Parameter
Parameter reset
Special
Display
Meaning
T_boiler
Heating flow temperature
T_return
Heating return temperature
T_outside
Outside temperature
T_header
Header temperature
T_DHW
DHW temperature
HC pressure
Heating circuit pressure
ZHP speed
PWM switching of the feed/heating circuit pump (ZHP)
Flow rate
Heating circuit flow rate
Notes:
Before a parameter reset, make a note of the settings and statistical data.
After the parameter reset, carry out a sensor calibration.
The sensor calibration function serves to balance out any deviations in the
measurements from the flow and return temperature sensors (T_boiler and T_return).
The temperature sensors are calibrated at the factory; sensor calibration is required
after replacing a sensor or carrying out a parameter reset.
Procedure:
Activation of the feed/heating circuit pump ZHP and correction of the flow temperature
sensor value (T_boiler) to the value of the return temperature sensor by setting
"FL correction".
For calibration, switch on ZHP, wait 10 minutes for the temperature to equalise, then
perform correction if necessary.
31.5 Special
Main menu
Submenu
Menu item
Chapter
Password for contractor level
Contractor
← back
Special
IDU service
ODU service
Fault history
Delete fault history
Special
Sensor calibration