61
3064298_201507
Contractor
parameter
Meaning
Setting range
Factory setting Individual setting
Compressor
WP080
BWL-1S(B)-07 dual mode point,
compressor
-20.0 °C ... 45.0 °C
-15.0 °C
WP080
BWL-1S(B)-10/14 dual mode point, compressor -20.0 °C ... 45.0 °C
-20.0 °C
Electric heater, add. ht. gen.
WP090
Enable electric heating for heating mode
Off, On
ON
WP091
Dual mode point, electric heating
-20.0 °C ... 45.0 °C
-5.0 °C
WP092
Power-OFF for electric heating
Off, On
On
WP093
Temporary deactivation of WP091
0 to 40 days
0 days
WP094
Type of electric heating
None, 2 kW, 3 kW,
4 kW, 6 kW, 9 kW
6 kW
WP101
Dual mode point, add. ht. gen.
-20.0 °C ... 45.0 °C
0.0 °C
Other
WP121
Max. compressor starts per hour
3 ... 10 / h
3 / h
31. Contractor level
* Contractor parameters are automatically pre-set depending on the selected system configuration.