60
3064298_201507
Contractor
parameter
Meaning
Setting range
Factory setting Individual setting
System
WP001
System configuration
01, 02, 05, 11, 12, 14,
15, 33, 34, 51, 52
01
WP002
Function input 1 (E1)
none
none
RT
DHW
RT/DHW
Zirkomat
TPW / Max Th
WP003
Function output 1 (A1)*
none
none
Timer20
Timer50
Timer100
Alarm
Zirkomat
Defrost
Add ht gn
Compressor ON
Heating HTG
WP010
Set spread / offset
0.0 ... 10.0 °C
5.0 °C
WP011
Heating hysteresis
0.5 ... 3.0 °C
2.0 °C
WP012
ZHP run-on
0 min ... 30 min
1 min
WP013
Delay for heating by add. ht generator, heating
1 min ... 180 min
60 min
WP014
HCP run-on
0 min ... 30 min
5 min
WP015
HC pump rate, maximum
70 % ... 100 %
100 %
WP016
Enabling spread control
Off, On
On
WP017
Max. boiler temp. HTG TV-max
40.0 ... 70.0 °C
55 °C
WP018
Min. boiler temp. BWT-min
10.0 ... 40.0 °C
20 °C
Domestic hot water DHW
WP020
Cylinder hysteresis
1.0 ... 10.0 °C
2.0 °C
WP021
Enable max. cylinder heating time
Off, On
ON
WP022
Max. cylinder heating time
30 min ... 240 min
120 min
WP023
Delay for heating by add. ht generator, DHW
1 min ... 180 min
60 min
WP024
Minimum DHW temperature
10.0 °C ... 55.0 °C
45.0 °C
Smart grid
WP025
Smart grid
Off, On
Off
WP026
External raising, HTG
0.0 - 20.0 °C
0.0 °C
WP027
External raising, DHW
0.0 - 20.0 °C
0.0 °C
WP028
External activation
Off, heat pump, heat
pump and electric
heating
Off
WP031
BUS address
1, 2, 3, 4, 5
1
Active cooling
WP053
Outside temp. enable cooling
15.0 … 40.0 °C
25.0 °C
WP054
Min. flow temp. for cooling
5.0 … 25.0 °C
20.0 °C
WP055
Offset set flow temp, cooling
5.0 … 20.0 °C
15.0 °C
WP058
Enable active cooling
Off, On
Off
31.3.1 Overview of contractor parameters for split heat pump:
(continued on next page)
31. Contractor level