![Wolf BML Operating Instructions Manual Download Page 8](http://html.mh-extra.com/html/wolf/bml/bml_operating-instructions-manual_991846008.webp)
3063527_201308
8
Installation as an external remote
control
Wall mounting base
installation
- Remove the wall mounting base from its packaging.
- Secure the wall mounting base on a flush-mounting box
(Ø 55 mm) or directly on the wall.
Wall mounting base
Fixing holes
Fixing holes
Installation of BML on wall mounting base
Wall mounting base
Mat. no. 2744275
60
100
Electrical connection of
remote control
- The electrical connection must be carried out only by a qualified
electrician.
- Never route sensor leads alongside mains power cables.
- Use the repair switch to switch off the power supply
- Wire the wall mounting base with a four-core cable (minimum
cross-section 0.5 mm²) in accordance with the diagram
eBUS
Terminal strip
Wall mounting base
+ -
+ -
Recommended
cables
and
minimum cable
cross-sections:
H05VV-F 3 x 2.5 mm²
power cable (230 V)
H05VV-F 4 x 1.0 mm²
Open/Close servomotor 230 V
H05VV-F 2 x 0.5 mm²
BUS cable (<400 m length)
Fuse/MCB protection:
Power supply 230 V 1 x 16 A
ϑ
Outside temperature sensor