Specialist parameter list - Overview
Parameter
Setting
range
Factory
setting
Individual
settings
LM001
Configuration
-
K20
LM013
Hysteresis OFF
0-3 K
1 K
LM015
Minimum fan speed
5 % - 60 %
30 %
LM016
Maximum fan speed
25 % - 100 %
70 %
LM017
P component for speed control
1 - 20
10
LM018
Ratio of extract air to supply air
fan speed
50 - 150
93
LM020
Weather-compensated
winter/summer changeover
ON/OFF
OFF
LM021
Differential for heating
1 K – 20 K
1 K
LM023
Room frost protection
ON/OFF
ON
LM024
Room frost protection
temperature
0 °C – 30 °C
5 °C
LM060
Fan speed for Economy
operation, speed control pre-
selection for backup mode, night
ventilation, summer mode, room
frost protection
40 % - 100 %
70 %
LM080
P component for heating circuit
mixer
5 - 20
12
LM081
Integral action time for heating
circuit mixer
0 - 25 min
2 min
Control level 3 - Specialist - System parameters
Setting parameters
With the r.h. rotary selector, select the required zone (from
zone 1 to 7) in the "Specialist" menu level (after entering a
password) and press selector to confirm.
Select the ventilation unit parameter (LM...) you want to
modify, confirm by pressing the selector and then modify
it by turning the r.h. rotary selector. Once you have set the
ventilation unit parameter (LM...) you wanted to modify, press
the r.h. rotary selector again to confirm the setting.
Specialist
Zone designat
LM001
K20
LM015
25 %
LM016
70 %
LM017
10 K
LM018
93
LM023
ON
Back