![Wolf BML Operating Instructions Manual Download Page 27](http://html.mh-extra.com/html/wolf/bml/bml_operating-instructions-manual_991846027.webp)
3063527_201308
27
LM100
Cascade effect
0 - 20
2
LM101
Integral action time for cascade
0 - 25 min
2 min
LM102
Supply air maximum limit
20 - 60 °C
50 °C
LM103
Control type
Supply air control,
cascade control
Supply air
control
LM114
Damper lead time
0 - 150 s
120 s
LM130
Night ventilation limit
10 - 30 °C
22 °C
LM131
Night ventilation start condition
differential TR > TA
2 K - 20 K
5 K
LM132
Night ventilation, minimum
outside temperature
5 - 20 °C
12 °C
LM150
P component for HR
5 - 20
12
LM151
Integral action time for HR
0 - 25 min
2 min
LM160
Air quality control
OFF/ON
ON
LM161
Air quality, start
0 - 10 V
4 V
LM162
Air quality, maximum
0 - 10 V
8 V
LM163
System OFF/ON via air quality
OFF/ON
OFF
LM180
Alarm function, fire dampers
(OFF) System
Off
(ON) Message
only
System OFF
LM190
Delay for
air flow fault
5 - 600 s
60 s
LM200
Active filter monitor
ON/OFF
OFF
LM201
Filter check interval
1 -10 weeks
1 week
LM202
Service message
via hours run
ON/OFF
OFF
LM203
Fan hours run
100 - 8000
1000
LM204
Filter check
ON/OFF
OFF
Parameter
Setting
range
Factory
setting
Individual
settings
Control level 3 - Specialist - System parameters