background image

DuoMix Installation Handbook

4

View

Mix 1 Demand

Mix 2 Demand

Minimum

Maximum

Melting

Idling

CWCO

°

F

Slab Supply

Sensor

Slab Return

Sensor

Slab Sensor

°

F

View

2

%

2

Mix 1 Demand

Mix 2 Demand

Minimum

Maximum

Melting

Idling

CWCO

°

F

View

2

%

2

Mix 1 Demand

Mix 2 Demand

Minimum

Maximum

Melting

Idling

CWCO

Melting mode

Once in melting mode, the DuoMix 201 maintains the slab at the programmed 

MELTING

temperature by controlling the speed of the  injection pump 2 (

Var2 Pmp). Whenever the control

is in the melting mode, the mixing pump (

Mix2 Pmp) is turned on and the Melting pointer is

displayed.

Idling mode

When the melting system starts off from a cold temperature, the time required for the slab to
reach the melting temperature can be excessive. To decrease this start up time, the slab can
be maintained at an idling temperature until melting is required. The idling feature is also useful
for preventing frost and light ice formation. When the control is in idling mode, the slab is
maintained at the IDLING temperature and the 

Idling pointer is turned on.

Warm Weather Cut Off (WWCO) 

If the slab and outdoor temperatures rise above the 

MELTING temperature, heating the slab is no longer required. The control therefore

shuts down the melting system. When the outdoor or slab temperature drops below the 

MELTING temperature, the control exits WWCO

and continues with normal operation.

Cold Weather Cut Off (CWCO) 

Maintaining the slab at a 

MELTING or IDLING temperature in extremely cold weather can be

expensive and may even be impossible. The control therefore turns the melting system off
when the outdoor temperature drops below the 

CWCO setting and turns on the CWCO pointer.

If the slab is at the desired 

MELTING temperature, the control will not enter the CWCO mode.

If the an enable signal is given during the 

CWCO mode, the control continues to melt once out

of the 

CWCO mode.

Slab Protection 

To protect the slab from cracking due to thermal stresses, the control limits the rate of heat
applied to the slab through a 

T MAX setting. The 

T represents the difference between the

measured slab supply and return fluid temperatures. If this temperature difference approaches
the 

T MAX setting,  the control operates the variable speed injection pump 2 to maintain the

T at the 

T MAX setting. The Maximum pointer  is turned on when the target 

T is greater than

the 

T MAX setting.

Ramping the 

T during Melting System Start Up

When the control is in melting mode, the control maintains the maximum 

T and slowly

increases the slab temperature to prevent thermal shock of the slab.

Run Time 

Prior to the control entering the snow melting mode, a 

RUN TIME should be selected. The snow melting time will start counting down once

the slab is up to melting temperature. If the 

Start button on the control or the Remote Display 040 is pressed while snow melting is enabled

and the slab is up to temperature, the run time counter is reset. Pressing the stop button on either control will end the snow melting
operation. Using the Snow Melting Enable Kit A3040039, pressing the button during warm up or run time will end the snow melt operation.

EXERCISING OF THE PUMPS

To prevent the pumps from seizing after long inactive periods, all pumps are turned on after every 3 days of no
operation. The 

Mix1 Pmp and Mix2 Pmp pump relays are turned on for 20 seconds and the variable speed pump

outputs are ramped up to 100% speed. During exercising, the LCD screen flashes "EXERCISE" and the 

Test LED

flashes. Exercising can be stopped by pressing the 

Test button.

REMOTE DISPLAY A3040040 (tN2). AVAILABLE OCTOBER 1998

A Remote Display A3040040 can be used to duplicate the control display in a remote location.
All settings can be remotely adjusted.

SNOW MELT ENABLE KIT A3040039 (tN2)

The Snow Melt Enable Kit is used for snow melting applications. The kit includes a Remote
Start/Stop Module, Mixing 2 Return Sensor A3040071, and a Slab Sensor A3040072. When
a Remote Start/Stop Module is connected to the 201, the LED (Light Emitting Diode) flashes
green or red. When the button is pressed, the control enters the snow melting mode. During
slab warm up, the LED flashes green. Once the slab is up to temperature, the LED remains
green continuously. If an error occurs in the control, the LED flashes red.

Installation

Slab Sensor 072

Universal Sensor 071

A3040071

A3040072

A3040040

Item

Menu

°

F

View

!

WWSD

1

%

%
2

Summary of Contents for DuoMix 201

Page 1: ...nditions the area experiences over the heating season If the heat demand is analyzed as a percentage of the heating systems capacity the heating system operates at or near maximum capacity for asmallp...

Page 2: ...thermally shocked Proper protection of the boiler under these circumstances requires modulating mixing devices that can temporarily reduce the heating load This is accomplished by reducing the speed o...

Page 3: ...er Protection A boiler sensor must be installed on the return line to the boiler in order to obtain boiler protection against flue gas condensation if required If the boiler return water temperature a...

Page 4: ...slab supply and return fluid temperatures If this temperature difference approaches the T MAX setting the control operates the variable speed injection pump 2 to maintain the T at the T MAX setting T...

Page 5: ...window openings In order to prevent heat that is transmitted through the wall from affecting the sensor reading it may be necessary to install an insulating barrier behind the enclosure The A3060070 s...

Page 6: ...e from the mixing 2 system pump to the Mix2 Pmp 8 terminal on the control Connect the second wire on the mixing 2 system pump to the N 7 terminal The control provides 120 V ac to the Mix2 Pmp contact...

Page 7: ...17 and 18 terminals on the control Slab Return Sensor 2 Ret2 Slab Return Sensor measures the return glycol temperature from the slab If the mixing 2 section is used for snowmelting connect the two wir...

Page 8: ...jection pump of the mixing 1 section is used make sure power to the terminal block is off and install a jumper between the terminals N Var1 Pmp 13 and 14 When power is applied to terminals the variabl...

Page 9: ...mixing 1 section will be skipped RST reset When using the mixing 1 section for building space heating the installer should select this adjustment The 201 control operates the mixing 1 section to provi...

Page 10: ...ly water temperature this setting must be selected The control operates the mixing 2 section to provide a fixed setpoint temperature equal to the SETPNT 2 temperature adjustment SNOW melting If sectio...

Page 11: ...ion pump to maintain the T at the T MAX setting The T MAX setting can be adjusted from 10 to 70 F 5 to 39 C Factory setting is 30 F CWCO Cold Weather Cut Off CWCO is the lowest temperature at which th...

Page 12: ...Pumps Displays when mixing pumps 1 or 2 are on 2 Warning Displays when an error is present Lock Unlock Displays whether keypad is locked or unlocked WWSD WWSD Displays when control is in Warm Weather...

Page 13: ...ng Idling CWCO 1 2 Target Mixing 2 Temperature Item Menu Start Stop F View Mix 1 Demand Mix 2 Demand Minimum Maximum Melting Idling CWCO 1 2 F 1 View Mix 1 Demand Mix 2 Demand Minimum Maximum Melting...

Page 14: ...Minimum Maximum Melting Idling CWCO 1 2 Outdoor temperature If a mixing 1 section is turned off the View Items from that section are skipped Dashes on the TARGET item denote heat is not required in th...

Page 15: ...Shut Down Desired Setpoint Temperature Item F Adjust Item F Adjust Design Outdoor Temperature F Adjust Adjust Mixing 2 Section Off Mixing 2 Section in Reset Mode Mixing 2 Section in Setpoint Mode Adju...

Page 16: ...e Maximum Supply Temperature F Adjust Misc Menu Units F C Item Misc Item Misc F Misc Display Contrast Display Backlight THE CONTROL AUTOMATICALLY GOES BACK TO THE VIEW MENU WHEN THE BUTTONS ARE LEFT A...

Page 17: ......

Page 18: ...Display Menu Cont...

Page 19: ...injection pump 2 Var 2 Pmp is ramped down to 0 over 10 seconds If the mixing 2 section is not used i e MODES 2 set to OFF N A is displayed and the pump is not operated STEP 6 The mixing 2 pump Mix2 P...

Page 20: ...l displays OUTDOOR SHRT When a fault with the outdoor sensor is present the control assumes a fixed outdoor temperature of 32 F During snow melting operation the control assumes an outdoor temperature...

Page 21: ...2 Boiler return short circuit 1 View 1 2 Boiler return sensor open circuit REFER TO THE TROUBLESHOOTING SECTION ABOVE FOR OPERATION DETAILS Return 2 Sensor Fault When the mixing 2 section is set to S...

Page 22: ...DuoMix Installation Handbook 22...

Page 23: ...DuoMix Installation Handbook 23...

Page 24: ...DuoMix Installation Handbook 24...

Page 25: ...DuoMix Installation Handbook 25...

Page 26: ...e it con tinually injects high temperature water at a fixed rate Text and diagrams used with permission from tekmar When the high temperature supply fluctuates and or varying water temperatures are re...

Page 27: ...the mixing occur directly after the point of injection downstream of the return to the hot loop See Figures 4 5 Advantages This type of system can use a small circulator to inject a high BTU input in...

Page 28: ...igures 4 5 show the two most common piping layouts for Variable Speed Injection Mixing Pay particular attention to the drop lines or thermal traps shown in the injection legs These are particularly im...

Page 29: ...rundfos 15 42 Speed 2 9 5 7 4 100 Taco 007 10 8 3 100 Grundfos Brute or 15 42 Speed 2 14 12 100 1 Taco 007 Grundfos Brute or 15 42 Speed 3 23 20 100 1 Grundfos 26 64 Taco 0010 35 31 100 1 Grundfos 43...

Page 30: ...DuoMix Installation Handbook 30...

Page 31: ...DuoMix Installation Handbook 31...

Page 32: ...DuoMix Installation Handbook 32...

Reviews: