TReX User Manual v2.14 Firmware
*TREX_TELEMETRY
Sets all parameters necessary to enable either the point to point serial link or back to back
mirror mode of operation.
*TREX_TELEMETRY=M,R,A,B,C
where:
M is telemetry mode of operation
0 = DISABLED,
1 = SERIAL_LINK,
2 = IO_MIRROR,
3 = SCADA_SLAVE,
4 = SCADA_MASTER
R is the number of remote TReX units when the telemetry mode is
SCADA_MASTER (valid 0-10)
A is the local unit ID (from 1-255).
B is the remote unit ID (from 1-255).
C is how long in seconds before sending all input information again.
Typical usage:
*TREX_TELEMETRY=0,0,1,2,10<CR>
*TREX_SCREEN
Sets the default main screen and the page for that main screen. On start-up the first screen
viewed is this screen. After a period of keypress inactivity, this is the return screen. This is
shown here only for completeness. Typically this would only be set through the MENU
system, and has no relevance when the TReX is being serially controlled.
*TREX_SCREEN=X,Y
where:
X = main screen
Y = page for that main screen.
Typical usage:
*TREX_SCREEN=0,0<CR>
*TREX_PIN
Sets the Personal Identification Number, which can be used to unlock the unit. The PIN
prevents accidental mis-configuration or changes by unauthorised users.
© WTE Limited, 2018 – Christchurch New Zealand
Page 80 of 158