TReX User Manual v2.14 Firmware
Where:
I = The input to configure (1-11 valid). Input 9 is the VIN input, 10 is ADC 1
and 11 is ADC 2.
: = the colon character ‘:’
N = number of transmissions (0 = no transmissions, 9 is max transmission count)
, = the comma character ‘,’
D = debounce in 100 ms steps (from 0-255)
, = the comma character ‘,’
R = time in seconds between retransmissions.
Typical usage:
*IN_CONFIG_H=1:1,10,15<CR>
*IN_MSG_L
Specifies the low level message that will be transmitted if configured. Input messages must
always use WT Protocol.
Typical usage:
.
*IN_MSG_L=1:WT1234560A10 IN_1_LOW<CR>
*IN_MSG_H
Specifies the high level message that will be transmitted if configured. Input messages must
always use WT Protocol.
Typical usage:
*IN_MSG_H=1:WT1234560A10 IN_1_HIGH<CR>
*IN_ANALOG
Specifies the high and low ADC count thresholds for an analog input to be considered a digital
HIGH or digital LOW. When these thresholds are exceeded, then programmed messages for
HIGH and LOW levels can be transmitted. All ADC counts are the SCALED ADC counts.
*IN_ANALOG=1H,1L,2H,2L,3H,3L
Where:
1H = Input voltage high (x10)
1L = Input voltage low (x10)
2H = ADC1 voltage high ADC count
2L = ADC1 voltage low ADC count
3H = ADC2 voltage high ADC count
© WTE Limited, 2018 – Christchurch New Zealand
Page 75 of 158