CHIMNEY – INSTALLATION
Continued:
Connection to an Existing Masonry Chimney
NOTE:
When inserting the stove pipe into the masonry chimney, be careful not to push it into the chim-
ney to far. If the stove pipe is in to far it will restrict the proper draft required for the furnace.
See figure 2
for the proper stovepipe position.
The connection between the WinterGreen Furnace and the chimney must be completed using a mini-
mum of 24 gauge UL Standard S-641 stovepipe and elbows. A clearance of at least 18 inches must be
maintained from all combustible surfaces.
(See figures 1 & 3)