5
088-00
60706-207
“Concealed Damage” is understood to mean dam-
age to the contents of a package which is not
evident at the time of delivery by the carrier, but
which is discovered later. The carrier or carriers are
responsible for merchandise lost or damaged in tran-
sit. The title to goods rests with the consignee when
generators are shipped F.O.B. factory, and only the
consignee can legally file a claim. Please note, most
carriers have a time limit for filing concealed damage
claims.
**** CAUTION ****
These units are shipped with oil. Be sure to check
oil levels before operating. See engine manufactur-
er’s instruction manual for recommended oil require-
ments before initial starting.
UNPACKING
. Carefully remove the carton.
2. After inspecting the engine-generator and trans-
fer switch for external physical damage, check
for the following items packed inside the carton.
a. Owner’s manual.
b. Engine manufacturer’s instruction manual.
3. Remove main frame hold down bolts. (4)
4. Unit can now be lifted from shipping pallet.
INSTALLATION
General Information
******************
***** WARNING *****
******************
Before proceeding with the installation be sure the
operation selector switch is in the stop position.
These engine generator sets are designed to be
mounted on a concrete pad outdoors only.
As an
option a prefab pad may be used as long as proper
attention is paid to site preparation to ensure the unit
will not move after installation. The transfer switch is
mounted next to your electrical entrance or distribu-
tion panel inside or outside the building. Consult a
qualified, licensed electrician or contractor to install
and wire the transfer switch.
The installation must
comply with all national, state and local codes.
Before beginning the installation process check the
rating of the generator set and its transfer switch
rating. Be certain they can handle the intended load
and are compatible with the entrance voltage, phase
and current ratings. Plans for installation should be
prepared with proper attention to mechanical and
electrical engineering detail to assure a satisfactory
system installation. The information in this manual is
offered only as a guide to finalizing your installation
plans.
SPECIFICATIONS
GENERATOR
MODEL WATTS*
VOLTS AMPS HZ PH RPM
PSS5
5000
20/240
62.5
60
3600
* Derate 6% for Natural Gas operation. Derate
3.5% per 000 feet elevation above sea level.
FUEL CONSUMPTION
NATURAL GAS
1000 BTU/CU FT
LP VAPOR
2520 BTU/CU FT
CF/HR
260
108
BTU/HR
260,000
272,160
GAL/HR
N/A
2.96
LBS/HR*
N/A
2.7
*
Based on full load operation.
LP TANK SIZING
Required LP tank size for LP Vapor withdrawal
operating at various outside temperatures given in
degrees Fahrenheit (Celsius).
TANK TEMPERATURE
TANK SIZE
60° F (16° C)
150 GALLON
32° F (0° C)
250 GALLON
0° F (18° C)
500 GALLON
-20° F (-29° C)
1000 GALLON
ENGINE SPECIFICATIONS
Refer to engine operating and maintenance instruc-
tions.
** NOTICE **
When unpacking the generator set, be sure to in-
spect it carefully for freight loss or damage. If loss or
damage is noted at the time of delivery, require that
the person making the delivery make note of the loss
or damage on the freight bill, or affix his signature
under the consignor’s memo of the loss or damage.
Contact the carrier for claim procedures.
When loss or damage is noted after delivery, segre-
gate the damaged material, and contact the carrier
for claim procedures. Be sure to retain the packag-
ing material for carrier inspection.
Summary of Contents for ULPSS15B2E
Page 1: ...11088 00 60706 207 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS15B2W E...
Page 10: ...11088 00 10 60706 207...
Page 18: ...11088 00 18 60706 207...
Page 22: ...11088 00 22 60706 207 ENGINE GENERATOR SET LAYOUT ULPSS15B2W E...
Page 23: ...23 11088 00 60706 207 ENGINE GENERATOR SET PAD LAYOUT...
Page 25: ...25 11088 00 60706 207 AC AND DC GENERATOR SCHEMATIC...
Page 26: ...11088 00 26 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...
Page 27: ...27 11088 00 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...