088-00
2
60706-207
The ground leads from all locations are connected to
the grounded terminal lugs also located on the side
wall. This set of terminals is labeled “GROUND”.
INSTALLATION NOTES
The load current carrying wires (L) and (T) must be
sized to handle the maximum load current without
excessive voltage drop. By code, the wire must be
heavy enough to handle the full current rating of the
main line circuit breaker (or fuse) in the entrance (or
sub-panel) protecting the contactor switch.
All wires should be installed in rigid or flexible con-
duit. Because of the many different types of service,
feeder, and distribution equipment, no specific wiring
instructions can be provided. It is, however, recom-
mended that
copper wire
be used. In all cases it is
essential that while the load is connected to the gen-
erator, there can be absolutely no feedback from the
generator to the power line or the power line to the
generator. When properly installed, the normal ATS
control and safety systems will eliminate all paths for
feedback. Check with your local electrical inspector
on applicable local, state and federal codes.
******************
***** WARNING *****
******************
A service disconnect must be installed in front of the
ATS panel as the ATS is not service entrance rated.
This will allow you to test the generator under load.
Should you ever have to work on the switch, you will
be able to disconnect the power and work on the
switch cold without having the power company pull
your meter.
To wire the automatic transfer switch into the exist-
ing wiring, first determine which circuits will be on
the emergency load circuit. If the entire load is to
be transferred, the transfer switch can be wired in
directly after the watt-hour meter and the service en-
trance, providing the service entrance ampere rating
is within the transfer switch’s rated capability.
If only specific circuits are to be powered under
emergency power failure conditions, an additional
distribution panel designated “emergency distribution
panel” must be installed.
All selected emergency circuits are removed from
main distribution panels and reinstalled in the emer-
gency distribution panel. Suggested circuits: freez-
er, refrigerator, furnace, emergency lights, sump
pump, emergency outlet circuits, etc. Total running
load must not exceed generator rating.
WIRE TEMPERATURE RATING
CU Connector
AL Connector
75° C
# 4 AWG
# 3 AWG
90° C
# 6 AWG
# 4 AWG
To gain access to the customer connections remove
the end door panel opposite the muffler. All AC and
DC connections to the ATS, 20 Volt power connec-
tion for battery charger, and battery installation are
made behind this panel. After removing the door
remove the cover over the customer connection box,
using a 7/6 inch open end wrench. See pages 20
and 2 for generator set and pad layout.
Two (2) hot leads, one () neutral and () ground
lead are required between the generator and the
ATS or distribution panel. The two power leads from
the generator are marked G and G3. Next install
two leads, one neutral and one ground lead from the
generator set to the ATS or distribution panel.
In addition to the power leads install a three wire 20
volt, 5 amp circuit from your distribution panel to
the generator. This circuit will be used to power the
battery charger, optional block heater and optional
battery heater.
The last two wires you will install are the DC control
leads (4 or 6 gauge) for the start circuit in the ATS.
These connections will be discussed later in more
detail.
WINCO UL ATS (ASCO 185)
See the ASCO installation manual for additional
details on proper wiring of the Automatic Trans-
fer Switch.
The standby generator terminals in the ATS are
marked “ALTERNATE L2 & L6”. The “hot” leads
G and G3 from the generator are connected to the
terminals L2 & L6.
The normal line power terminals in the ATS are
marked “PREFERRED - L & L5”. The “hot” line
power leads are L and L3 from your normal power
supply are connected to terminals L and L5.
The load terminals in the ATS are marked “LOAD
- L3 & L7”. The leads to the load distribution panel
are connected to terminals L3 & L7.
The neutral leads from all three locations are con-
nected to the isolated terminal lugs on the sidewall
of the cabinet. This terminal block is labeled “NEU-
TRAL” and the terminal lugs are mounted on red
isolation standoffs.
Summary of Contents for ULPSS15B2E
Page 1: ...11088 00 60706 207 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS15B2W E...
Page 10: ...11088 00 10 60706 207...
Page 18: ...11088 00 18 60706 207...
Page 22: ...11088 00 22 60706 207 ENGINE GENERATOR SET LAYOUT ULPSS15B2W E...
Page 23: ...23 11088 00 60706 207 ENGINE GENERATOR SET PAD LAYOUT...
Page 25: ...25 11088 00 60706 207 AC AND DC GENERATOR SCHEMATIC...
Page 26: ...11088 00 26 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...
Page 27: ...27 11088 00 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...