088-00
4
60706-207
DSE 3110 CONTROL
STOP/RESET (Red Button) This button places the module into its “Stop/
Reset” mode. This will clear any alarm conditions for which the triggering
criteria have been removed. The fuel supply de-energizes and the engine
comes to a standstill. Should a remote start signal be present while operating
in this mode, a remote start WILL NOT occur.
AUTO (White Button) This button places the module into its “Automatic”
mode. This mode allows the module to control the function of the generator
automatically. The module will monitor the remote start input and once a start
request is made, the set will be automatically started and placed on load. The
module will then wait until the next start event.
START (Green button)
Pressing this button from STOP/RESET will start the engine and run off load.
PAGE
Pressing this button scrolls the display to show the various instruments.
Summary of Contents for ULPSS15B2E
Page 1: ...11088 00 60706 207 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS15B2W E...
Page 10: ...11088 00 10 60706 207...
Page 18: ...11088 00 18 60706 207...
Page 22: ...11088 00 22 60706 207 ENGINE GENERATOR SET LAYOUT ULPSS15B2W E...
Page 23: ...23 11088 00 60706 207 ENGINE GENERATOR SET PAD LAYOUT...
Page 25: ...25 11088 00 60706 207 AC AND DC GENERATOR SCHEMATIC...
Page 26: ...11088 00 26 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...
Page 27: ...27 11088 00 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...