background image

10

OPM-108/B

A.C. ELECTRICAL CONNECTIONS

NOTICE: CLASS 1 WIRING METHODS ARE TO BE USED 

FOR ALL FIELD WIRING CONNECTIONS TO TERMINALS 

OF A CLASS 2 CIRCUIT

All wiring must be completed in accordance with the 

National Electric Code as well as any state and local codes.

You must pay particular attention to wire size requirement 

for the amperage of service you are dealing with. The table 

below provides you guidance on wire sizing based on both 

wire type and amperage. 

Wire amperages have been 

derated for 40° C ambient temperatures operation.

WARNING: 

Make sure the generator is disconnected from the battery to 

prevent accidental starting. 

A. NEUTRAL LUGS:

These lugs are isolated from ground and provided for you 

to connect your neutral wire from the transfer switch to the 

generator.

The 1200 Amp terminal block lugs on the 300-350kW will 

handle wire sizes #3/0 to 600 MCM and should be torqued 

to 28 ft. lbs. 

The 1000 Amp terminal block lugs on the 250kW will 

handle wire sizes #3/0 to 500 MCM and should be torqued 

to 28 ft. lbs. (Rated for 900 Amp for AL)

B. GENERATOR CIRCUIT BREAKER:

This circuit breaker provides overload protection for the 

generator. Your power feeds from the transfer switch 

12

5040-00

60708-166

MOUNTING THE AUTOMATIC 

TRANSFER SWITCH (A.T.S.)

    *************

*****  WARNING  *****

    ************* 

FIRE HAZARD - All wiring must be done by a licensed 

electrician, and must conform to the National Electrical 

Code and comply with all state and local codes and 

regulations.  Check with the local authorities before 

proceeding!

INSTALLATION NOTES

Because of the many different types of service, feeder, and 

distribution equipment, no specifi c wiring instructions can be 

provided.  It is recommended that only copper wire be used.

In all cases it is essential that while the load is connected to 

the generator, there can be absolutely no feedback from the 

generator to the power line or the power line to the generator.  

When properly installed, the normal A.T.S. Control and safety 

systems will eliminate all paths for feedback.

To wire the automatic transfer switch into the existing wiring, fi rst 

determine which circuits will be on the emergency load circuit.

If the entire load is to be transferred, the transfer switch can 

be wired in directly after the watt-hour meter and the service 

entrance, providing the service entrance ampere rating is within 

the transfer switch’s rated capability.  

If only specifi c circuits are to be powered under emergency 

power failure conditions, an additional distribution panel 

designated “emergency distribution panel” must be installed.

All selected emergency circuits are removed from main 

distribution panels and installed in the emergency distribution 

panel. The A.T.S. is then installed between the main panel and 

the emergency distribution panel.  Suggested circuits: freezer, 

refrigerator, furnace, emergency lights, sump pump, emergency 

outlet circuits, etc.  Total running load must not exceed generator 

rating.

A.C. ELECTRICAL 

CONNECTIONS

NOTICE - CLASS 1 WIRING METHODS ARE TO BE USED 

FOR ALL FIELD WIRING CONNECTIONS TO TERMINALS 

OF A CLASS 2 CIRCUIT

All wiring must be completed in accordance with the Nation 

Electric Code as well as any state or local codes.

You must pay particular attention to wire size requirement  for 

the amperage of service you are dealing with.  Appendix “2”  

provides you guidance on wire sizing based on both wire type 

and amperage.

 Wire amperage’s have been derated for 40

o

C

ambient temperatures operation.

A - Neutral Lugs, 

These neutral lugs are isolated from ground 

and provided for you to connect your neutral wire from the 

transfer switch to the generator.   

The 1200 amp terminal block lugs on the 300 to 350 kW will 

handle wire sizes #3/0 to 600 MCM and should be torqued to 28 

ft. lbs. 

The 1000 amp terminal block lugs on the  250 kW will handle 

wire sizes #3/0 to 500 MCM and should be torqued to 28 ft. lbs. 

(Rated for 900 AMP for AL)

B - Generator Circuit Breaker, 

This circuit breaker provides 

overload protection for the generator.  Your power feeds from 

the transfer switch will connect to the bottom lugs on the circuit 

breaker.  The generator power feeds have already been wired 

into the upper lugs.

Please refer to the circuit breaker installed on your unit for 

breaker lug capacities and proper torque specifi cations.

To select the proper conductor size between the Generator 

and the ATS, fi rst look your model up in Table 1 of Appendix 

“A” for your generator amperage. Then refer to Appendix “2” for 

guidance on wire sizing based on both wire type and amperage.   

Wire amperages have been derated for 40

o

C ambient 

temperatures operation.

For additional information on wire sizing refer to table 310-16 of 

the National Electrical Code ANSI/NFPA 70.

C - Ground Lug

, These ground lugs are bonded to ground 

and are provided for you to connect your ground wire from the 

transfer switch to.  The lugs will handle wire sizes #6 AWG to 300 

MCM  and should be torqued to 21 ft. lbs. 

CONNECTING BATTERY CHARGER & 
BLOCK HEATER

A three-stage battery charger is provided standard on 

this unit. The charger is an Automatic Battery Charger & 

Maintainer. This charger has three rates of charging. During 

the first mode, known as Bulk charging, the charging 

current is limited to 10 Amps at a voltage of up to 14/27 

Volts. The yellow LED will be on constantly during this 

stage. When the charging rate drops to 2.5 Amps, the 

charge will enter the ABSORPTION charging mode. During 

this mode, the yellow LED will be flashing. The charging 

voltage is held at 14/27 Volts and the charging rate 

gradually reduces the amount of current (Amps) flowing to 

the battery to 100% charged state. The battery can be left 

on this mode indefinitely. During this mode, the green LED 

will be on constantly. 

This charger is mounted under the customer connection 

on the control side of the generator and plugged into the 

receptacle mounted in the AC connection cabinet. The 

battery charger receptacle is to be powered by a GFCI 

circuit and installed in accordance with the United States 

National Electric Code. It is suggested that this circuit be 

fused for 15 amps. The block heaters on these units are 

1000 watt on the DR175 and 2250 watt on the larger units. 

The 2250 watt heaters and will require a separate 20 amp 

GFCI fused circuit. They are labeled Battery Charger Circuit 

and Block Heater Circuit.

The engine block heater installed on this unit should 

also be plugged in this receptacle. The block heater is 

thermostatically controlled and when plugged in will 

maintain the engine coolant temperature between 100 and 

120 degrees F.

MOUNTING THE AUTOMATIC 
TRANSFER SWITCH

WARNING: FIRE HAZARD:

All wiring must be done by a licensed electrician, and must 

conform to the National Electrical Code and comply with 

all the local codes and regulations. Check with the local 

authorities before proceeding.

INSTALLATION NOTES:

Because of many different types of service, feeder and 

distribution equipment, no specific wiring instructions can 

be provided. It is recommended that only copper wire 

be used. In all cases it is essential that while the load is 

connected to the generator, there can be absolutely no 

feedback from the generator to the power line or the power 

line to the generator. When properly installed, the normal 

ATS Control and safety system will eliminate all paths and 

feedback. 

To wire the automatic transfer switch into existing wiring, 

first determine which circuits will be on the emergency load 

circuit. If the entire load is transferred, the transfer switch 

can be wired directly after the watt-hour meter and the 

service entrance, providing the service entrance ampere 

rating is within the transfer switch’s rated capability.

If only specific circuits are to be powered under emergency 

power failure conditions, an additional distribution panel 

designated “emergency distribution panel” must be 

installed. 

All selected emergency circuits are removed from main 

distribution panels and installed in the emergency 

distribution panel. The ATS is then installed between 

the main panel and the emergency distribution panel. 

Suggested circuits: freezer, refrigerator, furnace, emergency 

lights, sump pump, emergency outlet circuits, etc. Total 

running load must not exceed generator rating.

Summary of Contents for DR175F4

Page 1: ...s unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE __________________...

Page 2: ...s loaded to its full capacity and the voltage current and frequency are carefully checked Rated output of generator is based on engineering tests of typical units and is subject to and limited by the...

Page 3: ...ion or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings on the unit labels and...

Page 4: ...ns Fuel ASTM D 975 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 29 6 Quarts Cooling System 50 50 mix DR300F4 Generator Wattage 300 000 300 000 300 000 Volts 120 208 120 2...

Page 5: ...otal system s performance and reliability The engine generator set consists of a multi cylinder liquid cooled engine nominally operating at 1800 rpm The generator frequency regulation is maintained by...

Page 6: ...dash mark The base component of the model numbering system identifies an engine type engine starting method fuel type kilowatt rating engine manufacturer and number of generator poles Following the s...

Page 7: ...dling equipment i e a forklift CAUTION Do not attempt to lift the generator set by the means of the lifting eyes on the engine or generator end These lifting points are only for the use during the man...

Page 8: ...t of the enclosure In addition to a hot air discharge you must plan a fresh air intake opposite the radiator discharge Their fresh air inlets should be 1 to 2 times larger than the radiator face The e...

Page 9: ...ircuit the battery charging system on the engine CAUTION A battery presents a risk of electrical shock and high short circuit current The following precautions must be observed when working with batte...

Page 10: ...er The generator power feeds have already been wired into the upper lugs Please refer to the circuit breaker installed on your unit for breaker lug capacities and proper torque speci cations To select...

Page 11: ...operating switch is in the OFF position WARNING EQUIPMENT DAMAGE When installing a three phase 240 Volt system be sure you know which lead is the high voltage wild leg 208 Volt line to neutral The ge...

Page 12: ...s present the common alarm LED if configures will illuminate The LCD display will show an icon to indicate the failure WARNINGS Warnings are non critical alarm conditions and do not affect the operati...

Page 13: ...he line power should fail or be turned off the transfer switch during manual operation the load may be applied to the generator With the engine running smoothly check the no load voltage and frequency...

Page 14: ...of the cylinder block Discharge the coolant inside the engine 4 Close the drain cock and the water drain plug Refill radiator with coolant MAINTENANCE CHANGING THE OIL CAUTION PERSONAL INJURY Only cha...

Page 15: ...the fluid until only fuel comes out 4 Fully hand tighten the plug 5 Dispose of liquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will...

Page 16: ...the injection pump channels 4 Connect the fuel circuit to a tank containing CFB protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine for approx 2 min...

Page 17: ...fective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water...

Page 18: ...he red Light Emitting Diode LED is illuminated refer to the Under Frequency Roll Off UFRO adjustment 7 Carefully turn VOLTS control clockwise until rated voltage is reached 8 If instability is present...

Page 19: ...N THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 202...

Page 20: ...20 OPM 108 B ENGINE HARNESS SCHEMATIC DR175F4...

Page 21: ...21 OPM 108 B ENGINE HARNESS SCHEMATIC DR250F4...

Page 22: ...8 2 2 9 4958 36 9 8 89 9 8 77 77 67 57 1 6723 6723 6 5 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 4 25 46 53354 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 9 5 92 7 8670 17 5 267 7 9...

Page 23: ...EE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THRE...

Page 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Reviews: