Warning alarms are self-resetting when the fault condition 

is removed. The icon will appear steady in the display.

SHUTDOWN

Shutdowns are critical alarm conditions that stop the 

engine and draw the operator’s attention to an undesirable 

condition. Shutdown alarms are latching. The fault must be 

removed and the STOP/RESET button pressed to reset the 

module. The icon will be flashing in the display.

INITIAL START UP

WARNING: EQUIPMENT DAMAGE:

Before attempting  to start this unit, complete your pre-start 

checklist and ensure the generator mainline circuit breaker 

is in the proper position prior to starting. Starting this unit 

without it properly connected can cause serious personal 

injury or equipment damage.

DO NOT jump start these engine-generator sets. Starting 

these units on a low battery or jump starting them will 

cause damage to the engine control module. 

Use the following check list to verify correct installation 

before starting the engine.

 

 Engine oil. Fill as required with proper grade/qty.

 

 Engine coolant. Fill as required with proper mixture.

 

□ 

Unit mounting base properly bolted down.

 

 Clearance for service and maintenance on all sides.

 

 Proper fuel line material and size.

 

 All fuel line connections tight.

 

 Battery connections clean and tight

 

 Battery fully charged.

 

 All AC and DC wiring installed and properly 

   protected.

 

 Compressor oil. Fill as required with proper grade/

   qty.

After completing the previous checklist, the engine-

generator set is ready for initial start-up. 

MANUAL MODE

1. Press and release the Manual Mode button. The small 

LED light 

next to it should come on. 

Note:

 There is no start delay in this mode of operation.

2. Press and release the green Start Engine button. The 

DSE 7310 MKII will send two signals to the engine. The first 

signal wire #21 will engage the fuel solenoid, the second 

wire, #22, will engage the starter on the engine. At this 

point the DSE7310 will start the cranking cycle (10 seconds 

on and 10 seconds off).

Note: Wire #93 is energized to turn on the glow plugs for 

15 seconds first and then the starter and fuel solenoid are 

engaged.

If the engine fails to start during this cranking period, the 

starter motor is disengaged and goes into a rest mode after 

which a second attempt is made to start the engine. Should 

this sequence continue through 3 cranking cycles the start 

sequence will be stopped and the display will show ‘FAILED 

TO START”. 

3. During manual operation, the load will not normally be 

applied to the generator. But caution must be used, if the 

line power should fail or be turned off the transfer switch 

during manual operation the load may be applied to the 

generator.

With the engine running smoothly check the no load 

voltage and frequency on the digital display. The voltage 

should be 208/240/480 AC depending on which model 

you have and a frequency of 59.5 to 60.5 hertz (Hz). 

If you have the proper voltage at the generator the next 

step is to check the voltage at the generator terminals in 

the Automatic Transfer Switch. The voltage between the 

G1 and the G3 terminals should be the same as it was 

on the generator front panel. The voltage should also be 

checked between the hot terminals (G1 and G3) and the 

G-N to be certain of a balanced voltage output and a solid 

neutral connection. The voltage between G1 and G-N 

should be about 120 volts AC (277 on 480 units). The same 

approximate voltage should be found between terminals 

G3 and G-N (120 volts AC).

On three phase panels the G2 voltage level should also be 

checked. ON 240 VOLT (DELTA) SYSTEMS BE SURE YOU 

KNOW WHERE THE HIGH VOLTAGE “WILD” LEG IS. IT 

MUST BE IN THE SAME LOCATION ON THE LINE SIDE AS IT 

IS ON THE GENERATOR SIDE. 

(i.e. if it’s on L-3 on the line side it must be on G-3 on the 

generator side. Also on three phase systems make sure that 

the rotation is the same on the generator as it is on your 

line power. Failure to insure proper rotation will cause three 

phase motors to spin backwards possibly damaging them.

NOTICE:

If for any reason during the check out procedure the 

voltage and frequency are not correct, depress the STOP/

RESET button and correct the trouble before proceeding.

4. Stopping - There are two ways to stop the unit when it is 

in the manual mode. Pressing the STOP/RESET button will 

stop the unit immediately. Pressing the AUTO mode button 

will stop the unit but only after the cool down timers have 

timed out and there is no remote start signal being sent to 

the unit.

AUTO MODE

To activate the automatic start mode you will just need to 

depress the AUTO button, the LED indicator beside the 

button confirms that the unit is in automatic mode.

To test the Automatic Transfer Switch, follow the instruction 

on the operator’s manual that came with the transfer 

switch. If you get a fault during the initial start up or prior 

to start up, it is most likely a false warning light. Simply reset 

the ATS start over.

Once you have completed testing of the ATS, be sure you 

ALWAYS leave the system in the standby mode,unless 

servicing the unit. For standby operation, press the AUTO 

button on the front of the control. The green light should 

light up next to the AUTO button.

NOTE: For setting the exerciser circuit, for all ATS, see the 

operator’s manual shipped with the ATS. 

Summary of Contents for DR175F4

Page 1: ...s unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE __________________...

Page 2: ...s loaded to its full capacity and the voltage current and frequency are carefully checked Rated output of generator is based on engineering tests of typical units and is subject to and limited by the...

Page 3: ...ion or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings on the unit labels and...

Page 4: ...ns Fuel ASTM D 975 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 29 6 Quarts Cooling System 50 50 mix DR300F4 Generator Wattage 300 000 300 000 300 000 Volts 120 208 120 2...

Page 5: ...otal system s performance and reliability The engine generator set consists of a multi cylinder liquid cooled engine nominally operating at 1800 rpm The generator frequency regulation is maintained by...

Page 6: ...dash mark The base component of the model numbering system identifies an engine type engine starting method fuel type kilowatt rating engine manufacturer and number of generator poles Following the s...

Page 7: ...dling equipment i e a forklift CAUTION Do not attempt to lift the generator set by the means of the lifting eyes on the engine or generator end These lifting points are only for the use during the man...

Page 8: ...t of the enclosure In addition to a hot air discharge you must plan a fresh air intake opposite the radiator discharge Their fresh air inlets should be 1 to 2 times larger than the radiator face The e...

Page 9: ...ircuit the battery charging system on the engine CAUTION A battery presents a risk of electrical shock and high short circuit current The following precautions must be observed when working with batte...

Page 10: ...er The generator power feeds have already been wired into the upper lugs Please refer to the circuit breaker installed on your unit for breaker lug capacities and proper torque speci cations To select...

Page 11: ...operating switch is in the OFF position WARNING EQUIPMENT DAMAGE When installing a three phase 240 Volt system be sure you know which lead is the high voltage wild leg 208 Volt line to neutral The ge...

Page 12: ...s present the common alarm LED if configures will illuminate The LCD display will show an icon to indicate the failure WARNINGS Warnings are non critical alarm conditions and do not affect the operati...

Page 13: ...he line power should fail or be turned off the transfer switch during manual operation the load may be applied to the generator With the engine running smoothly check the no load voltage and frequency...

Page 14: ...of the cylinder block Discharge the coolant inside the engine 4 Close the drain cock and the water drain plug Refill radiator with coolant MAINTENANCE CHANGING THE OIL CAUTION PERSONAL INJURY Only cha...

Page 15: ...the fluid until only fuel comes out 4 Fully hand tighten the plug 5 Dispose of liquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will...

Page 16: ...the injection pump channels 4 Connect the fuel circuit to a tank containing CFB protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine for approx 2 min...

Page 17: ...fective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water...

Page 18: ...he red Light Emitting Diode LED is illuminated refer to the Under Frequency Roll Off UFRO adjustment 7 Carefully turn VOLTS control clockwise until rated voltage is reached 8 If instability is present...

Page 19: ...N THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 202...

Page 20: ...20 OPM 108 B ENGINE HARNESS SCHEMATIC DR175F4...

Page 21: ...21 OPM 108 B ENGINE HARNESS SCHEMATIC DR250F4...

Page 22: ...8 2 2 9 4958 36 9 8 89 9 8 77 77 67 57 1 6723 6723 6 5 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 4 25 46 53354 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 9 5 92 7 8670 17 5 267 7 9...

Page 23: ...EE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THRE...

Page 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Reviews: