background image

12

OPM-147/C

distribution panels and installed in the emergency 

distribution panel. The ATS is then installed between 

the main panel and the emergency distribution panel. 

Suggested circuits: freezer, refrigerator, furnace, emergency 

lights, sump pump, emergency outlet circuits, etc. Total 

running load must not exceed generator rating.

DC WIRING

All communication and DC wiring should be run in 

separate conduit from AC wiring.

To install the wires, reference the following picture. Use a 

small flat head screwdriver to push the release spring inside 

the square hole (A). While the release is being pushed, 

insert the wire into the larger circular hole (B). Remove the 

screwdriver to secure the wire into place.

REMOTE START

The DSE7310 is able to start the generator when it receives 

a remote signal from any dry contact. This makes the system 

compatible with a wide range of control mechanisms 

including two-wire start automatic transfer switches. When 

the contact closes the controller will automatically start. 

When the contact is opened the generator will go through 

a cool-down cycle and turn off.  Connect the remote start 

leads to the Remote Start + and Remote Start - terminal 

blocks in the door behind the DSE 7310 controller. 

Depending on the distance, 14 to 16 gauge stranded wire 

should be used. It is suggested that these wires be labeled 

S1 and S23. 

Note: Any relay closure can be used to start and stop this 

generator. As long as the contact stays closed the engine 

generator set will continue to run. Once the relay is opened 

the unit will shut down and remain in the standby mode 

until the remote start relay is closed again.

A

B

SCR 

(DSENET)

4A 

(DSENET)

4B 

(DSENET)

Battery Charge Fail Emergency Stop Emergency Stop Remote S

tart +

Remote S

tart -

Ground Ground B Battery -

Two-Wire Start Hook-Ups

E STOPS

In some applications additional emergency stops may be 

desired or necessary. The controller has terminals designed 

allowing the addition of multiple remote emergency stops. 

E-stops must be normally closed to work properly in this 

system. The e-stop circuit supplies power to fuel solenoid 

and the starter circuit. Opening any switch in the series 

prevents the engine from cranking or from receiving fuel to 

run. 

To wire additional emergency stop switches first remove 

the orange jumper between the two Emergency Stop 

terminal blocks. Failure to remove the jumper will prevent 

the remote switches from working properly. Add wires 

between the terminal block to the new switch(s). The 

switches must be wired in series for proper function. Test 

each e-stop after wiring to ensure they function properly.

SERIAL COMMUNICATION

DSE provides a series of remote accessories that can help 

provide useful information to operators. These accessories 

communicate over the DSE Net. Terminal blocks are wired 

to the distribution panel to aid in installation. Follow the 

instructions included with each accessory.

The generator controller can communicate with a variety 

of controls and monitoring systems, including RS232 and 

RS485. The ports are wired onto the back of the DSE7310. 

In order to finalize communication the program will need 

to be adjusted using the free DSE configuration software to 

enable the commutation. Contact Winco service for a list of 

register values.

INSTALLING THE BATTERY

CAUTION

In the following battery installation procedure, check to be 

sure the engine control is in the “stop” position. This should 

be your last step before initial start-up.

A customer supplied 12 Volt battery is required to complete 

the installation. Installation of the highest CCA rated battery, 

within the correct BCI group, will increase cold weather 

starting performance.

BATTERY REQUIREMENTS

Voltage

BCI Group

Min. CCA Rating

12

24

650

SCR 

(DSENET)

4A 

(DSENET)

4B 

(DSENET)

Battery Charge Fail Emergency Stop Emergency Stop Remote Start + Remote Start - Ground Ground B Battery -

E-Stops

Summary of Contents for DE2314 Series

Page 1: ...ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ P...

Page 2: ...ERATIONS COLD WEATHER OPERATIONS MAINTENANCE 19 CHANGING THE OIL CHANGING OIL FILTER CHANGING COOLANT REFILLING COOLANT CHANGING AIR FILTER CHECKING WATER IN FUEL FILTER CLEANING RADIATOR CHANGING THE...

Page 3: ...AZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or us...

Page 4: ...120 240 277 480 Phase Single Three Three Three PF 1 0 0 8 0 8 0 8 Amps 82 71 62 31 Hertz 60 60 60 60 ENGINE Model Isuzu 4LE2T Starting System 12 Volt Fuel Consumption full load 2 1 Gal hr Fuel ASTM D...

Page 5: ...e series star connected Exciter Rotor 0 201 per phase Exciter Stator 14 7 DE40I4 STANDBY MODEL DE40I4 03 DE40I4 04 DE40I4 17 DE40I4 18 DE40I4 21 Watts 36 000 39 000 39 000 39 000 39 000 Volts 120 240...

Page 6: ...e information recorded inside the front cover of this manual for future reference and for identification whenever requesting field or factory assistance Primary fields needed for assistance are comple...

Page 7: ...ction manual c Start up and warranty validation form d Battery hold down brackets hardware e Unit components or accessory items shipped loose for on site installation f Optional accessories 3 Remove m...

Page 8: ...ible to lift the generator from the radiator side It requires especially long forks and care should be taken to ensure that no contact is made with the radiator Pushing the radiator will cause damage...

Page 9: ...eriorate and the unit mountings will come loose These units must be mounted to a steel or concrete base VENTILATION REQUIREMENTS WARNING EQUIPMENT DAMAGE It is the installer s responsibility to ensure...

Page 10: ...he fuel inlet pump If your fuel supply is lower than 3 feet you may have to install an additional lift pump to bring the fuel up to the mechanical fuel pump on the engine The information in this manua...

Page 11: ...rator should only supply equipment that is cord and plug connected through customer installed receptacles mounted on the generator or the vehicle PERMANENTLY INSTALLED GENERATORS This WINCO portable g...

Page 12: ...emergency stops may be desired or necessary The controller has terminals designed allowing the addition of multiple remote emergency stops E stops must be normally closed to work properly in this syst...

Page 13: ...1 Always wear full eye protection and protective clothing 2 Where electrolyte contacts skin wash off immediately with water 3 If electrolyte contacts the eyes flush thoroughly and immediately with wa...

Page 14: ...f Auto Maintain Mode The illuminated Green auto maintain LED This indicates your 12volt battery is fully charged During short or long term storage periods Auto Maintain Energy Saver mode will monitor...

Page 15: ...Authorized Monograde CAUTION PERSONAL INJURY Only check oil when the engine is not running and is at a low temperature in order to avoid the risk of burns 1 Remove the dipstick and ensure the oil lev...

Page 16: ...n 480 units The same approximate voltage should be found between terminals G3 and G N 120 volts AC On three phase panels the G2 voltage level should also be checked ON 240 VOLT DELTA SYSTEMS BE SURE Y...

Page 17: ...e initial start up or prior to start up it is most likely a false warning light Simply reset the ATS to start over Once you have completed testing of the ATS be sure you ALWAYS leave the system in the...

Page 18: ...testing program can also provide early warnings or oil degradation Efforts may need to be made to reduce the amount of dust and debris entering the housing and generator components COLD WEATHER OPERA...

Page 19: ...e of the cylinder block Discharge the coolant inside the engine MAINTENANCE CHANGING THE OIL CAUTION PERSONAL INJURY Only change oil when the engine is not running and is at a low temperature in order...

Page 20: ...AMAGE Clean the exhaust valve prior to checking the pre filter to reduce the risk for system contamination Do NOT perform while the engine is running 1 Place a container for collecting liquids under t...

Page 21: ...he previous paragraph 6 Close all of the engine s intake discharge ventilation and bleeding holes with plugs or seal them with adhesive tape 7 Drain the residual 30 M protective oil from the sump whic...

Page 22: ...fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water temper...

Page 23: ...THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 50 65 85 100 115 130 150 175 200 230...

Page 24: ...ANK 95 SP 5V4 109 SG 5VRT4 100 SG SLD5 98 IF CAM 101 SG 5VRT5 65 IA THCO 70 IA OILPRESS 84 IA THW 93 IS EBMPOS 2 94 IS EBMPOS 1 99 IS EBMPOS 3 25 IS ENGSTP 28 IS IDLUP 27 IS IDLMNL 26 IS IDLDWN 49 IS...

Page 25: ...5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 56 6 2 1 29...

Page 26: ...26 OPM 147 C THREE PHASE AC WIRE HIGH AND LOW WYE WIRING DIAGRAMS...

Page 27: ...27 OPM 147 C THREE PHASE AC WIRING DELTA SINGLE PHASE 311 WINDING...

Page 28: ...oduct that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EXPRESS WARRANTIES O...

Reviews: