Commissioning
78
WILO SE 2018-12
DANGER
Risk of explosion if the switchgear is installed in potentially explosive
areas!
The switchgear does not have its own explosion protection class and must always be
installed outside of potentially explosive areas! The connection must be made by a
qualified electrician.
8.3
Connection of signal transmitters
and pumps within potentially ex-
plosive atmospheres
DANGER
Risk of explosion due to incorrect connection!
If pumps and signal transmitters are connected in explosive atmospheres, there is a
risk of explosion due to incorrect connection. Observe the section on explosive at-
mospheres in the appendix!
8.4
Activating the device
NOTICE
Error message during operation at the alternating current connection
The switchgear has a rotating field monitor and motor current monitor. Both monit-
oring functions only work trouble-free at the three-phase current connection and
are activated at the factory. If the switchgear is used at an alternating current con-
nection, the following error messages are shown in the display:
• Rotating field monitoring: Error code “E006”
⇒ Switching off rotating field monitoring: Select Menu 5.68, value “off”!
• Motor current monitoring: Error code “E080.x”
⇒ Switching off the motor current monitoring: Select Menu 5.69, value “off”!
▶ Monitoring functions deactivated. The switchgear now works trouble-free at the
alternating current connection.
NOTICE
Observe the error code in the display
If the red fault LED lights up or flashes, observe the error code on the display! If the
error has been confirmed, the previous error is stored in menu 6.01.
NOTICE
Operating mode after power failure
Following a power failure, the switchgear will automatically start up in the last oper-
ating mode set.
‡
Switchgear is closed.
‡
Installation has been performed correctly.
‡
All signal transmitters and consumers are connected and installed in the operating
space.
‡
If float switches are used, set the switching points correctly.
‡
Motor protection is preset according to the pump data.
1. Turn the main switch to the “ON” position.
2. Switchgear starts.
All LEDs light up for 2 s.
– The display illuminates and the start screen appears.
- The standby symbol appears in the display.
Summary of Contents for Wilo-Control EC-L
Page 2: ......
Page 3: ...3 Deutsch 4 English 54 Fran ais 104 Polski 156 P 207 WILO187690...
Page 209: ...ru Wilo Control EC L 209 1 1 1 1 2 1 3 1 4 www wilo com legal 2...
Page 210: ...ru 210 WILO SE 2018 12 2 1 1 2 2...
Page 211: ...ru Wilo Control EC L 211 2 3 2 4 2 5 IP 2 6 IP54 30 C 50 C 90 2 7 2 8 16 18 3...
Page 216: ...ru 216 WILO SE 2018 12 1 2 3 4 5 6 6 4 3 IPS 6 4 4 Extern OFF 6 4 5 6 4 6 3 01 Extern OFF...
Page 223: ...ru Wilo Control EC L 223 6 5 8 Fig 14 Fig 15 6 5 9 Fig 16...
Page 225: ...ru Wilo Control EC L 225 Fig 19 SBM 250 1 A 6 5 13 SSM Fig 20 SSM 250 1 A 6 5 14 EBM...
Page 233: ...ru Wilo Control EC L 233 8 3 8 4 E006 5 68 off E080 x 5 69 off 6 01...
Page 247: ...ru Wilo Control EC L 247 7 OFF 8 9 4 1 2 3 4 5 6 10 10 1 10...
Page 252: ...ru 252 WILO SE 2018 12 www wilo recycling com 13 13 1 13 1 1 1 2 0 13 1 2 Ex i 13 1 3...
Page 260: ......
Page 261: ......
Page 262: ......