en
Operation
76
WILO SE 2018-12
Level measurement with level sensor or dynamic pressure bell
4
Extern OFF
5
3
1
2
Fig. 27:
Illustration of the switching points with
a level sensor in the “fill” operating mode using
the example of one pump
1
Pump On
2
Pump Off
3
High water level
4
Min. water level
5
Dry-running level in the well
A level sensor or dynamic pressure bell can be connected. This can be used to control
three pumps:
▪ Pump 1 On/Off
▪ Pump 2 On/Off
▪ Pump 3 On/Off
▪ Min. water level in the tank to be filled
▪ High water level
▪ Dry-running level in the well (separate float switch at the “Extern OFF” input)
7.3
Menu control
Fig. 28:
Operating button function
The menu is controlled via the operating button:
▪
Turn:
Menu selection or settings values.
▪
Press:
Change menu level, confirm error number or value.
7.4
Menu type: Main menu or Easy Ac-
tions menu
There are two different menus.
▪ Main menu: Access to all settings for a complete configuration.
▪ Easy Actions menu: Quick access to certain functions.
Observe the following points when using the Easy Actions menu:
– The Easy Actions menu only offers access to the selected functions. It is not possible
to perform a complete configuration with this.
– Perform an initial configuration to use the Easy Actions menu.
– The Easy Actions menu is enabled at the factory. Note, the Easy Actions menu can be
disabled in menu 7.06
.
7.5
Call up the menu
Call up the main menu
1. Press operating button for 3 seconds.
▶ Menu item 1.00 appears.
Call up the Easy Actions menu
1. Turn operating button 180°.
⇒ The “Resetting error messages” or “Manual operation pump 1” function ap-
pears
2. Turn operating button an additional 180°.
▶ The other functions are shown. The main screen appears at the end.
7.6
Quick access to “Easy Actions”
The following functions can be called up using the Easy Actions menu:
Summary of Contents for Wilo-Control EC-L
Page 2: ......
Page 3: ...3 Deutsch 4 English 54 Fran ais 104 Polski 156 P 207 WILO187690...
Page 209: ...ru Wilo Control EC L 209 1 1 1 1 2 1 3 1 4 www wilo com legal 2...
Page 210: ...ru 210 WILO SE 2018 12 2 1 1 2 2...
Page 211: ...ru Wilo Control EC L 211 2 3 2 4 2 5 IP 2 6 IP54 30 C 50 C 90 2 7 2 8 16 18 3...
Page 216: ...ru 216 WILO SE 2018 12 1 2 3 4 5 6 6 4 3 IPS 6 4 4 Extern OFF 6 4 5 6 4 6 3 01 Extern OFF...
Page 223: ...ru Wilo Control EC L 223 6 5 8 Fig 14 Fig 15 6 5 9 Fig 16...
Page 225: ...ru Wilo Control EC L 225 Fig 19 SBM 250 1 A 6 5 13 SSM Fig 20 SSM 250 1 A 6 5 14 EBM...
Page 233: ...ru Wilo Control EC L 233 8 3 8 4 E006 5 68 off E080 x 5 69 off 6 01...
Page 247: ...ru Wilo Control EC L 247 7 OFF 8 9 4 1 2 3 4 5 6 10 10 1 10...
Page 252: ...ru 252 WILO SE 2018 12 www wilo recycling com 13 13 1 13 1 1 1 2 0 13 1 2 Ex i 13 1 3...
Page 260: ......
Page 261: ......
Page 262: ......