Commissioning
en
Installation and operating instructions Wilo-Control EC-L
85
Fig. 59:
Menu 1.12
Menu no.
1.12*
Description
Base-load pump On level
Value range**
0.06 … 12.5 m
Factory setting
0.40 m
Explanation
Operating mode “drain”: Value must be 0.03 m
higher
than
the “Base-load pump Off level” (menu 1.13).
Operating mode “fill”: Value must be 0.03 m
lower
than the
“Base-load pump Off level” (menu 1.13).
Fig. 60:
Menu 1.13
Menu no.
1.13*
Description
Base-load pump Off level
Value range**
0.06 … 12.5 m
Factory setting
0.23 m
Explanation
Operating mode “drain”: Value must be 0.03 m
lower
than
the “Base-load pump On” level (menu 1.12).
Operating mode “fill”: Value mandatory 0.03 m
higher
than
the “Base-load pump On level” (menu 1.12).
Fig. 61:
Menu 1.14
Menu no.
1.14*
Description
Level peak-load pump 1 on
Value range**
0.06 … 12.5 m
Factory setting
0.42 m
Explanation
Operating mode “drain”: The value must be 0.03 m
higher
than the “Peak-load pump 1 On” level (menu 1.15). The
switch-on level must be
greater than/equal to
the switch-
on level of the base-load pump (menu 1.12).
Operating mode “fill”: The value must be 0.03 m
lower
than
the “Peak-load pump 1 Off” level (menu 1.15). The switch-
on level must be
lower than/equal to
the switch-on level
of the base-load pump (menu 1.12).
Fig. 62:
Menu 1.15
Menu no.
1.15*
Description
Peak-load pump 1 Off level
Value range**
0.06 … 12.5 m
Factory setting
0.25 m
Explanation
Operating mode “drain”: Value mandatory 0.03 m
lower
than the “Peak-load pump 1 On” level (menu 1.14). The
switch-off level must be
greater than/equal to
the switch-
on level of the base-load pump (menu 1.13).
Operating mode “fill”: Value must be 0.03 m
higher
than
the “Peak-load pump 1 On” level (menu 1.14). The switch-
off level must be
lower than/equal to
the switch-off level
of the base-load pump (menu 1.13).
Fig. 63:
Menu 1.16
Menu no.
1.16*
Description
Peak-load pump 2 On level
Value range**
0.06 … 12.5 m
Factory setting
0.42 m
Explanation
Operating mode “drain”: The value must be 0.03 m
higher
than the “Peak-load pump 2 Off” level (menu 1.17). The
switch-on level must be
greater than/equal to
the switch-
on level of the peak-load pump (menu 1.14).
Operating mode “fill”: The value must be 0.03 m
lower
than
the “Peak-load pump 2 Off” level (menu 1.17). The switch-
on level must be
lower than/equal to
the switch-on level
of the peak-load pump (menu 1.14).
Summary of Contents for Wilo-Control EC-L
Page 2: ......
Page 3: ...3 Deutsch 4 English 54 Fran ais 104 Polski 156 P 207 WILO187690...
Page 209: ...ru Wilo Control EC L 209 1 1 1 1 2 1 3 1 4 www wilo com legal 2...
Page 210: ...ru 210 WILO SE 2018 12 2 1 1 2 2...
Page 211: ...ru Wilo Control EC L 211 2 3 2 4 2 5 IP 2 6 IP54 30 C 50 C 90 2 7 2 8 16 18 3...
Page 216: ...ru 216 WILO SE 2018 12 1 2 3 4 5 6 6 4 3 IPS 6 4 4 Extern OFF 6 4 5 6 4 6 3 01 Extern OFF...
Page 223: ...ru Wilo Control EC L 223 6 5 8 Fig 14 Fig 15 6 5 9 Fig 16...
Page 225: ...ru Wilo Control EC L 225 Fig 19 SBM 250 1 A 6 5 13 SSM Fig 20 SSM 250 1 A 6 5 14 EBM...
Page 233: ...ru Wilo Control EC L 233 8 3 8 4 E006 5 68 off E080 x 5 69 off 6 01...
Page 247: ...ru Wilo Control EC L 247 7 OFF 8 9 4 1 2 3 4 5 6 10 10 1 10...
Page 252: ...ru 252 WILO SE 2018 12 www wilo recycling com 13 13 1 13 1 1 1 2 0 13 1 2 Ex i 13 1 3...
Page 260: ......
Page 261: ......
Page 262: ......