Commissioning
80
WILO SE 2018-12
7
1
5
3
2
Fig. 31:
Parameter input enabled
1. Press the operating button for 3 s.
⇒ Menu item 1.00 appears
2. Turn the operating button until menu 7 appears.
3. Press the operating button.
⇒ Menu 7.01 appears.
4. Press the operating button.
5. Change value to “on”: Turn the operating button.
6. Save value: Press the operating button.
⇒ The menu is enabled and can be changed.
7. Turn the operating button until the end of menu 7 appears.
8. Press the operating button.
⇒ Back to the main menu level.
▶ Start initial configuration:
– Menu 5: Basic settings
– Menu 1: Switch-on/off values
– Menu 2: Field bus connection (if applicable)
- Menu 3: Enable pumps
Menu 5: Basic settings
Fig. 32:
Menu 5.01
Menu no.
5.01
Description
Operating mode
Value range
fill (fill), drain (drain)
Factory setting
drain
Fig. 33:
Menu 5.02
Menu no.
5.02
Description
Number of connected pumps
Value range
1 … 3
Factory setting
2
Fig. 34:
Menu 5.03
Menu no.
5.03
Description
Standby pump
Value range
on, off
Factory setting
off
Explanation
One pump can be used as the standby pump. This pump is
not activated in normal operation. The standby pump is
only activated in the event of pump failure due to a fault.
The standby pump is subject to standstill monitoring. The
standby pump is therefore activated during pump cycling
and pump kick.
Fig. 35:
Menu 5.07
Menu no.
5.07
Description
Signal transmitter for level measurement
Value range
Float, Level, Bell, Opt01
Factory setting
Level
Explanation
Definition of the signal transmitters for level measurement:
- Float = float switch
- Level = level sensor
- Bell = dynamic pressure bell
- Opt01 = NW16 level monitor
Summary of Contents for Wilo-Control EC-L
Page 2: ......
Page 3: ...3 Deutsch 4 English 54 Fran ais 104 Polski 156 P 207 WILO187690...
Page 209: ...ru Wilo Control EC L 209 1 1 1 1 2 1 3 1 4 www wilo com legal 2...
Page 210: ...ru 210 WILO SE 2018 12 2 1 1 2 2...
Page 211: ...ru Wilo Control EC L 211 2 3 2 4 2 5 IP 2 6 IP54 30 C 50 C 90 2 7 2 8 16 18 3...
Page 216: ...ru 216 WILO SE 2018 12 1 2 3 4 5 6 6 4 3 IPS 6 4 4 Extern OFF 6 4 5 6 4 6 3 01 Extern OFF...
Page 223: ...ru Wilo Control EC L 223 6 5 8 Fig 14 Fig 15 6 5 9 Fig 16...
Page 225: ...ru Wilo Control EC L 225 Fig 19 SBM 250 1 A 6 5 13 SSM Fig 20 SSM 250 1 A 6 5 14 EBM...
Page 233: ...ru Wilo Control EC L 233 8 3 8 4 E006 5 68 off E080 x 5 69 off 6 01...
Page 247: ...ru Wilo Control EC L 247 7 OFF 8 9 4 1 2 3 4 5 6 10 10 1 10...
Page 252: ...ru 252 WILO SE 2018 12 www wilo recycling com 13 13 1 13 1 1 1 2 0 13 1 2 Ex i 13 1 3...
Page 260: ......
Page 261: ......
Page 262: ......