2.2

Staff training

The personnel installing the pump must have the appropriate
qualifications for this work.

2.3

Risks incurred by failure to comply with the safety
precautions

Failure to comply with the safety precautions could result in per-
sonal injury or damage to the pump or installation. Failure to
comply with the safety precautions could also invalidate any
claim for damages.
In particular, lack of care may lead to problems such as:
– Failure of important pump or machinery functions,
– Injury resulting from electrical or mechanical factors.

2.4

Safety precautions for the operator

Existing regulations for the prevention of accidents must be fol-
lowed.
Dangers caused by electrical energy are to be excluded. Di-
rectives conforming to the local or general regulations and the
local electricity supply companies are to be observed.

2.5

Safety information for inspection and assembly

The operator is responsible for ensuring that inspection and as-
sembly are carried out by authorised and qualified personnel
who have studied the operating instructions closely.
Work on the pump/machinery should only be carried out when
the machine has been brought to a standstill.

2.6

Unauthorized modification and manufacture of spare
parts

Alterations to the pump or installation may only be carried out
with the manufacturer's consent. The use of original spare parts
and accessories authorised by the manufacturer will ensure sa-
fety. The use of any other parts may invalidate claims invoking
the liability of the manufacturer for any consequences.

2.7

Unauthorised operating methods

The operating safety of the pump or installation supplied can
only be guaranteed if it is used in accordance with paragraph
1 of the operating instructions. The limiting values given in the
catalogue or data sheet must neither be exceeded nor allowed
to fall below those specified.

3. Transport and storage

The pump should be protected against moisture
and physical damage during transport and interim
storage.

The pump should be transported using authorised
transportation equipment. They are to be attached
to the pump flanges and if necessary to the motor
outer diameter (protection against slipping requi-
red!). 
The ring bolts on the motor must only be used when
carrying a load.

The ring bolts on the motor must only be used for
transporting the motor, not the entire pump.

ATTENTION!

4. Description of product

and accessories

4.1

Description of pump 

Single-stage low-pressure centrifugal pump of monobloc de-
sign. Two kinds of drive motors are optionally available:
– IEC standard motor directly coupled to pump stub shaft with

adaptor support between pump and motor (Fig.1).

– Motor with extended single motor/pump shaft (Fig.2).
Both versions feature a vibration-free compact unit. The pump
housing is of inline design with suction and discharge ports axi-
ally in line. The shaft is sealed by a mechanical seal. The pump
can be mounted directly in the sufficiently supported pipework.

DPL:

Two pump heads mounted in a common housing (twin
pump), the pump housing being of Inline design. When
used in conjunction with an automatic variable speed
controller only the base-duty pump is operated varia-
bly. The second pump remains available for parallel
operations to cover peak-load demand and additionally,
for standby duty to take over under fault conditions.

4.2

Scope of supply

– Pump / twin pump complete,
– Installation and maintenance instructions.

5. Siting/ Installation

5.1

Installation

– Siting in a dry, well ventilated envionment,
– Pump to be placed in an easily accessible position in order

to facilitate inspections and exchange.

– Minimum space of 15 cm between a surface and the motor

fan cover.

– Maxmum ambient temperature 40 °C.
– Before pump installation, all welding/soldering on the pipe

system must be completed and the pipe system be flushed
out thoroughly to be clear of all foreign matter and impurities.

– Ensure that the pump is not stressed by the pipework
– The pump can be installed in any pipe run course, horizon-

tal or vertical, as long as the motor does not face downwards.

– Arrows at the pump indicate water flow direction through the

pump.

– It is recommended to provide and install isolating valves at

suction and discharge ports of the pump in order to avoid
draining to the whole pipe system in the case of pump in-
spections or excharge.

– The lantern is equipped with a plugged tapping for a possi-

bly drain conncetion for condensation.

– When assembling pumps with all-purpose flange PN6/10 the

following guidelines are to be observed (fig. 4):

1.

It is not permitted to assemble all-purpose flanges with all-
purpose flanges.

2.

enclosed plain washers (pos. 1) 

must

be used between the

screw/nut head and the all-purpose flange.

Safety elements (e.g lock washers) are not per-
mitted.

ATTENTION!

ENGLISH

8

Summary of Contents for DPL N Series

Page 1: ...stallation and operating instructions F Notice de montage et de mise en service NL Montage en bedieningsvoorschrift E Instrucciones de instalaci n y funcionamiento I Istruzioni di montaggio use e manu...

Page 2: ......

Page 3: ...Fig 1 IPL N Fig 2 IPL...

Page 4: ...Fig 3 Fig 4...

Page 5: ...tructions 7 Notice de montage et de mise en service 10 Montage en bedieningsvoorschriften 14 Instrucciones de instalaci n y funcionamiento 18 Istruzioni di montaggio uso e manutenzione 22 Montasje og...

Page 6: ......

Page 7: ...steme WILO CR DR System 3 x Motor Sonderausf hrung Sonderspannung frequenz X Pumpe Ex gesch tzt nur Ausf hrung N X 1 2 2 Anschlu und Leistungsdaten Schl ssel x Standardausf hrung X Sonderausf hrung bz...

Page 8: ...ber oder unterschritten werden 3 Transport und Zwischenlagerung Die Pumpe ist bei Transport und Zwischenlagerung gegen Feuchtigkeit und mechanische Besch di gung zu sch tzen Der Transport der Pumpe i...

Page 9: ...ihrem Betriebspunkt und der Dampfdruck des F rdermediums Pumpen durch L sen der Entl ftungsventile Bild 1 2 Pos 9 entl ften Ein Trockenlauf zerst rt die Gleitringdichtung Je nach Temperatur des F rder...

Page 10: ...le aufstecken Neuen O Ring Pos 8 einlegen Motor mit Laufrad und Wellendichtung in das Pumpenge h use einsetzen und mit den Flanschschrauben Pos 11 be festigen Motor anklemmen Armaturen vor und hinter...

Page 11: ...ear Wilo CR DR systems 3 x Special design motor Special voltage frequency X Pump Flame Explosion proof N version X Legend x Standard supply X Special design or accessories at added cost on request 1 W...

Page 12: ...motor must only be used for transporting the motor not the entire pump ATTENTION 4 Description of product and accessories 4 1 Description of pump Single stage low pressure centrifugal pump of monoblo...

Page 13: ...li cenced electrician in strict conformity with ruling re gulations Check that the power supply is suitable conforming with the data on the pump rating plate Power supply 3 400 415 V 50 Hz Network fus...

Page 14: ...from shaft Remove stationary seal ring from its seat in the motor flange and thoroughly clean seat face Thoroughly clean part of shaft Re Assembly Refit new stationary seal ring into motor flange Refi...

Page 15: ...int gr 2 X Modification r glage de la vitesse de rotation Commutation de p les X Apparails de r glage Syst me Wilo CR DR 3 x Mod le sp ciale de moteur Tension fr quence sp ciale X Pompe Protection an...

Page 16: ...e Pendant le transport et le stockage avant utilisation prot ger la pompe contre l humidit et tout dom mage m canique Le transport de la pompe doit tre effectu au moyen d un dispositif de suspension a...

Page 17: ...nt la vis de d gazage figure 1 2 Pos 9 La garniture m canique d tanch it sera d truite en cas de marche sec Selon la temp rature du fluide et la pression du sy st me lorsqu on ouvre la vis de d gazage...

Page 18: ...arbre Placer l entretoise Pos 6 sur l arbre Monter la roue hydraulique Pos 2 sur l arbre Mettre en place le circlips neuf Pos 7 sur l arbre de la pompe Mettre en place un nouveau joint torique Pos 8...

Page 19: ...motoruitvoering afwijkende spanning frequentie X pomp ex beveiligd alleen uitvoering N X 1 2 2 Aansluit en kapaciteitsgegevens uitvoeringstabel sleutel x standaard uitvoering X speciale uitvoering op...

Page 20: ...in geen geval worden onder of overschreden 3 Transport en tussenopslag De pomp moet tijdens het transport en de tijdelijke opslag worden beschermd tegen vocht en mechani sche beschadiging Het transpor...

Page 21: ...geval buizen en of de pomp raakt het aansluitschema voor de elektrische aansluiting bevindt zich in het klemmenkastendeksel de toepassing van een motorbeveiligingsschakelaar wordt aanbevolen 6 Inbedr...

Page 22: ...rbehouden NEDERLANDS Montagevork verwijderen de motorkabel aansluiten afsluiters voor en achter de pomp openen eventuele zekeringen en of de hoofdschakelaar inschakelen pomp in bedrijf stellen echter...

Page 23: ...2 X Regulaci n conmutaci n de la velocidad Conmutation de polos X Cuadro de regulaci n Sistema WILO CR DR 3 x Ejecuci n especial s del motor Tensi n frecuencia especiales X Bomba Protecci n antidefla...

Page 24: ...amiento Los valores l mite que figuran en el cat logo o en la ficha t c nica no deben ser nunca ni superiores ni inferiores a los espe cificados 3 Transporte y almacenaje Deber protegerse la bomba dur...

Page 25: ...ento de la bomba y debe ser determinada de acuerdo con las mismas Los valores NPSH de la bomba en su punto de trabajo y la presi n de vapor del medio de impulsi n son par metros esenciales a la hora d...

Page 26: ...cte las bornas al motor y abra los dispositivos de corte delante y detr s de la bomba Conecte los fusibles y siga las instrucciones para la puesta en servicio apartado 6 Cambio del cierre mec nico en...

Page 27: ...cessario a cura del committente x Protezione integrale incorporata WSK Semiconduttore 2 X Variazione regolazione della velocit Commutazione die poli X Apparecchiature di regolazione systemi WILO CR DR...

Page 28: ...ti o accessori non originali pu pregi udicare la sicurezza e far decadere la garanzia 2 7 Condizioni di esercizio non consentito La sicurezza di funzionamento delle apparecchiature assicu rata solo pe...

Page 29: ...lla pompa Verificare i dati di targa della pompa Alimentazione 3 230V 400V 50Hz Fusibili di rete 16A ritardati Curare la messa a terra della pompa Lo schema di collegamento alla rete si trova nella mo...

Page 30: ...rraggio Con riserva di modificia ITALIANO Rimuovere la forchetta di montaggio Ripristinare i collegamenti elettrici Riaprire gli organi di intercettazione Seguire le istruzioni del capitolo 6 inerenti...

Page 31: ...lsomkobling regulering Polomkobling X Reguleringssystemer WILO CR DR system 3 x Spesialutf relse motor Spesialspenning frekvens X Pumpe Eksplosjonssikker bare utf relse N X N kkel x Standardutf relse...

Page 32: ...d adapterst tte mellom pumpe og motor Figur 1 Motor med hel aksel til pumpen Figur 2 Begge utf relser er kompakte enheter med svak vibrasjon Pumpehuset er utf rt IN LINE dvs at flensene p innsugings o...

Page 33: ...2 p akselen Sett ny seegerring pos 7 p pumpeakselen Sett p en ny O ring pos 8 Sett koblingsstykket med l pehjulet og akselpakningen inn i pumpehuset og skru til Fest motoren ved hjelp av flensskruene...

Page 34: ...nt 3 230V 3 400 V 50 Hz x Suojaluokka IP 55 x Moottorinsuoja Tarvitaan x Integroitu moottorin t yssuoja WSK KLF 2 X aihtuvanopeuksinen k ytt Moninopeuksinen moottori X Ohjausj rjestelm t WILO CR DR j...

Page 35: ...saa miss n tapauksessa ylitt tai alittaa 3 Kuljetus ja v livarastointi Pumppu on suojattava kosteudelta sek mekaani silta vaurioilta kuljetuksen ja v livarastoinnin yhtey dess Pumpun kuljetus on suor...

Page 36: ...uolen kanssa kytkem ll pumppu hetkellisesti p lle Mik li py rimissuunta on v r niin vaihda sis ntu vien vaihejohtimien paikat kesken n 7 Huolto 7 1 Liukurengastiiviste Totutusajon kuluessa merkitykset...

Page 37: ...aa sulkuventtiilit ennen pumppua ja sen j lkeen Kytke sulake takaisin Toista k ytt noton toimenpiteet kappale 6 SUOMI Irroita asennushaarukka Kytke uudelleen virtajohtimet kytkent rasiassa Avaa sulkuv...

Page 38: ...34...

Page 39: ...ed according annex I No 1 5 1 of the EC Machinery directive 2006 42 EC Les objectifs protection de la directive basse tension sont respect es conform ment appendice I n o 1 5 1 de la directive CE rela...

Page 40: ...n sleduj c m p slu n m ustanoven m Niniejszym deklarujemy z pe n odpowiedzialno ci e dostarczony wyr b jest zgodny z nast puj cymi dokumentami Sm rnice ES pro strojn za zen 2006 42 ES dyrektyw maszyn...

Page 41: ...00 wilo wilo hu India WILO India Mather and Platt Pumps Ltd Pune 411019 T 91 20 27442100 service pun matherplatt co in Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 citrawilo cb...

Page 42: ...henstra e 100 44263 Dortmund T 0231 4102 7900 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 kundendienst wilo com T glich 7 18 Uhr erreichbar 24 Stunden Technische Notfallunterst tzung Kundendienst...

Reviews: