background image

48 

WILO SE 05/2016 V05 DIN A4

English 

MAINTENANCE AND REPAIR

2.  Switch off the entire unit so it is voltage-free and 

secure it against accidental activation.

3.  If the terminals for SBM, SSM and HW are occu-

pied, the external voltage source present there 

must also be switched so it is voltage-free.

4.  Disconnect all power supply cables and pull these 

out of the threaded cable connections.

5.  Connect the ends of the power supply cables so 

that no moisture can enter into the cable.

6.  Dismount the switchgear by undoing the screws 

on the substructure or on the pedestal.

8.3.1.  Return delivery/storage

For shipping purposes, the switchgear must be 

packaged so it is protected against knocks and 

waterproof.

Please also refer to the “Transport and storage” 

section.

8.4.  Disposal

Proper disposal of this product avoids damage to 

the environment and risks to personal health.

• Use the services of public or private waste dis-

posal companies, or consult them for the disposal 

of the product or parts thereof.

• For more information on proper disposal, please 

contact your local council or waste disposal offi ce 

or the supplier from whom you obtained the 

product.

9.  Maintenance and repair

POTENTIALLY fatal danger due to electrical 

voltage!

When performing work on the uncovered 

switchgear, there is a risk of fatal electric 

shocks occurring. During all work, the switch-

gear must be disconnected from the electric-

ity network and secured against reactivation 

without permission. All electrical work must 

be carried out by a qualifi ed electrician.

After completing maintenance or repair work, 

the switchgear must be connected according to 

the “Installation” section and activated as under 

“Commissioning”.

Maintenance or repair work and/or con-

structional changes that are not listed in this 

operating and maintenance manual may only be 

carried out by the manufacturer or by author-

ised service centres.

9.1.  Maintenance intervals

To ensure reliable operation, various maintenance 

tasks must be carried out regularly.

NOTE

When used in sewage lifting units inside build-

ings or on land plots, the maintenance intervals 

and work shown in DIN EN 12056‐4 must be 

adhered to.

Before initial commissioning or after a longer 

period of storage:

• Clean switchgear

Yearly

• Inspect contactor contacts for melting

9.2.  Maintenance tasks

Prior to maintenance work, the switchgear must 

be switched off as described under “Temporary 

shutdown”. Maintenance work may only be car-

ried out by qualifi ed persons.

9.2.1.  Clean switchgear

Use a damp cotton cloth to clean the switchgear.

Do not use any aggressive or scouring cleaners 

or fl uids!

9.2.2.  Inspect contactor contacts for melting

Have the contacts checked for melting by a quali-

fi ed electrician or Wilo Customer Service.

If more serious combustion is ascertained, have 

the affected contacts replaced by a specialist 

electrician or Wilo Customer Service.

9.3.  Repairs

Prior to repair work, the switchgear must be 

switched off as described under “Final shutdown” 

and all power supply cables dismantled. Repair 

work must be carried out by an authorised service 

centre or Wilo Customer Service.

10. Troubleshooting and possible solutions

DANGER due to electrical voltage!

Improper procedures during electrical work 

may result in fatal injuries caused by electrical 

voltage! This work may only be carried out by 

a qualifi ed electrician.

Possible faults are displayed for 30 seconds on 

the display using an alphanumeric code. Accord-

ing to the fault shown, the connected pump or 

signal transmitter must be checked for correct 

operation and replaced if necessary.

Only perform this work if suitably qualifi ed 

personnel are available. Electrical work must be 

carried out by qualifi ed electricians for instance.

We recommend always having this work carried 

out by Wilo Customer Service.

Unsanctioned modifi cations to the switchgear are 

made at the operator's own risk and release the 

manufacturer from any warranty obligations.

10.1. Fault indication

Overview of symbols:

E06

Error code

Error icon

Faults are displayed in various ways:

Summary of Contents for Control SC-L

Page 1: ...otice de montage et de mise en service es Instrucciones de instalaci n y funcionamiento it Istruzioni di montaggio uso e manutenzione pt Manual de Instala o e funcionamento nl Inbouw en bedieningsvoor...

Page 2: ...Fig 2B Fig 2A Fig 1 1 2 3 4 1 2 3 3 4 5 6 6 7 1 2 3 3 4 6 5 7...

Page 3: ...Fig 4 Fig 3 Fig 5 dry run 4 all OFF 3 P1 ON 1 P2 ON 2 high water 5 5 P1 OFF 2 P1 ON 1 P2 ON 3 P2 OFF 4 6 7 8 low water 4 dry run Ext OFF 5 OFF 3 ON 1 2 high water...

Page 4: ...erating modes and operation principle 40 6 2 Menu control and structure 41 6 3 Initial commissioning 41 6 4 Setting the operating parameters 41 6 5 Forced switching of the pumps in case of dry run or...

Page 5: ...ual refers to the switchgear indicated on the title page 1 5 Warranty In general the specifications in the current Gen eral Terms and Conditions apply to the warranty You can find these here www wilo...

Page 6: ...must be shut down immediately by the operator Tools and other objects should be kept in their designated places The switchgear may not be installed in potentially explosive areas There is a risk of e...

Page 7: ...LED indicators The switchgear comprises the following main components Main switch for switching the switchgear on off Control panel LEDs for displaying the current operating state operation fault LC d...

Page 8: ...sion for pumps and signal transmitters used in potentially explosive areas 3 7 Options Connection for 3 or 4 pumps Customer specific adjustments for special appli cations 3 8 Scope of delivery Switchg...

Page 9: ...by a qualified electrician The installation location must be clean dry and free of vibrations Avoid exposing the switchgear to direct sunlight The customer must provide the power supply cables These m...

Page 10: ...using the level sensor the switching point must be set via the menu A forced switch off of the pumps always occurs irrespective of the selected signal transmitter 5 3 5 High water alarm The high water...

Page 11: ...otection be set 5 above the current measured at the duty point Star delta activation Set the motor protection to 0 58 x the rated current The maximum start up time in star connection is 3 seconds Pump...

Page 12: ...2 5 m Display range 0 2 5 m Setting 1 V 0 25 m Insert the cable ends of the cable laid on site through the threaded cable connections and secure accordingly Connect the wires to the terminal strip acc...

Page 13: ...ed Fig 4 Illustration of the switching points with a level sensor in the Empty operating mode using the example of two pumps 1 Base load pump ON 5 Dry running protection 2 Base load pump OFF 6 High wa...

Page 14: ...All terminals must be retightened Motor protection correctly set The separate HAND 0 AUTO switch for each pump must be set to AUTO A The factory setting for these is 0 OFF Switching on 1 Turn main sw...

Page 15: ...2 4 Peak load pump 1 off Value range 0 06 to 12 42 Factory setting 0 50 1 2 2 5 Peak load pump 2 on Value range 0 09 to 12 45 Factory setting 1 00 1 2 2 6 Peak load pump 2 off Value range 0 06 to 12...

Page 16: ...2 2 x Running time of the individual pumps 4 2 3 0 Unit switching cycles 4 2 4 x Switching cycles of the individual pumps 4 3 0 0 Details of switchgear 4 3 1 0 Switchgear type 4 3 2 0 Serial number as...

Page 17: ...6 1 0 General pump cycling Values ON OFF Factory setting ON 5 6 2 0 Pump cycling after time interval Values ON OFF Factory setting OFF 5 6 3 0 Running time of base load pump until pump cycling Value...

Page 18: ...tion Run At least one pump is running Menu 5 5 2 0 SSM The required logic of the collective fault signal can be set Fall negative logic falling edge Rise positive logic rising edge Menu 5 6 0 0 Pump c...

Page 19: ...ide potentially explosive areas 7 3 Activating the switchgear NOTE Following a power supply interruption the switchgear will automatically start up in the last operating mode set 1 Turn main switch to...

Page 20: ...hand the cover must be opened There is a risk of fatal injury due to live parts This work may only be carried out by a qualified electrician In case of a control failing the individual pumps can be sw...

Page 21: ...nsure reliable operation various maintenance tasks must be carried out regularly NOTE When used in sewage lifting units inside build ings or on land plots the maintenance intervals and work shown in D...

Page 22: ...ected pump was tripped Remedy See installation and operating instructions for the connected pump request these from Wilo customer service E20 x Fault Temperature monitor for motor winding Cause Motor...

Page 23: ...r in power supply phase error incorrect rotat ing field low voltage Error in motor winding WSK PTC impermeability External off Pump Pump 1 Pump 2 Pump 3 Pump 4 Pump cycling Time dependent pump cycling...

Page 24: ...d pump 3 Activation threshold Peak load pump Delay time for activation Peak load pump 1 Deactivation threshold Peak load pump 2 Deactivation threshold Peak load pump 3 Deactivation threshold Peak load...

Page 25: ...0 071 24 15 0 0 087 6 15 0 0 063 12 15 0 0 052 18 15 0 0 045 24 18 5 0 059 6 18 5 0 043 12 18 5 0 035 18 22 0 0 046 6 22 0 0 033 12 22 0 0 027 18 11 3 Spare parts Spare parts can be ordered from Wilo...

Page 26: ......

Page 27: ...ot kompatybilno ci elektromagnetycznej 2004 108 WE 2004 108 EG Sm rnice pro n zk nap t 2006 95 ES dyrektyw niskonapi ciow 2006 95 WE 2006 95 EG pou it harmoniza n normy zejm na stosowanymi normami zha...

Page 28: ......

Page 29: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: