OPERATION AND FUNCTION
4. Display of parameters currently set as well as data
for the switchgear (type, serial number etc.)
5. Basic settings for the switchgear
6. Fault memory
7. Service menu (can only be activated by Wilo
customer service)
The menu structure is adapted automatically
based on the signal transmitters used. Menu
1.2.2.0 is only visible for instance if a level sensor
is connected and activated accordingly in the
menu.
6.4.1. Menu structure
1. Start the menu by pressing the operating knob
for 3 sec.
2.
Choose the selected menu: Easy or Expert.
3. Follow the menu structure below for the desired
value and change this according to your specifi -
cations.
Menu 1: Control parameters
No.
Description
Display
1.1.0.0
Operating mode
1.1.1.0
Selection:
empty
fi ll
1.2.0.0
Control values
1.2.2.0
Threshold for activation/deac-
tivation level (only available if a
level sensor is used)
1.2.2.1
Base-load pump on
Value range: 0.09 to 12.45
Factory setting: 0.62
1.2.2.2
Base-load pump off
Value range: 0.06 to 12.42
Factory setting: 0.37
1.2.2.3
Peak-load pump 1 on
Value range: 0.09 to 12.45
Factory setting: 0.75
1.2.2.4
Peak-load pump 1 off
Value range: 0.06 to 12.42
Factory setting: 0.50
1.2.2.5
Peak-load pump 2 on
Value range: 0.09 to 12.45
Factory setting: 1.00
1.2.2.6
Peak-load pump 2 off
Value range: 0.06 to 12.42
Factory setting: 0.75
1.2.2.7
Peak-load pump 3 on
Value range: 0.09 to 12.45
Factory setting: 1.25
Menu 1: Control parameters
No.
Description
Display
1.2.2.8
Peak-load pump 3 off
Value range: 0.06 to 12.42
Factory setting: 1.00
1.2.5.0
Delay times for activation and
deactivation of the pumps
1.2.5.1
Base-load pump stop delay
Value range: 0 to 60
Factory setting: 5
1.2.5.2
Peak-load pump(s) activation
delay time
Value range: 1 to 30
Factory setting: 3
1.2.5.3
Peak-load pump(s) stop delay
Value range: 0 to 30
Factory setting: 1
1.2.5.4
Stop delay at dry-running level
Value range: 0 to 10
Factory setting: 0
1.2.5.5
Activation delay time after dry
run
Value range: 0 to 10
Factory setting: 1
1.2.5.6
System activation delay time
after power interruption
Value range: 0 to 180
Factory setting: 0
Menu 2: Communication parameters
No.
Description
Display
2.0.0.0
Communication
2.1.0.0
Field bus
Values: None, Modbus, BACnet,
GSM
Factory setting: None
Menu 3: Pump activation
No.
Description
Display
3.0.0.0
Pump activation
3.1.0.0
Switching automatic mode on/
off
Values: ON, OFF
Factory setting: OFF
3.2.0.0.
Operating mode per pump
3.2.x.0
Selection of pump 1 ... 4
Summary of Contents for Control SC-L