OPERATION AND FUNCTION

Menu 5: Basic switchgear settings

No.

Description

Display

5.2.5.0

Priority when dry run and high 

water signals are present simul-

taneously**

Values: Dry Run, High Water

Factory setting: Dry Run

5.2.6.0

Signal detection for level con-

trol**

Values: Floater, Sensor

Factory setting: Sensor

5.4.0.0

Limit values

5.4.1.0

Dry run level

Value range*: 0.01 to 12.39

Factory setting: 0.12

5.4.2.0

High water alarm level

Value range*: 0.12 to 12.50

Factory setting: 1.50

5.4.4.0

High water alarm delay

Value range: 0 to 30

Factory setting: 0

5.4.5.0

Running time monitoring of indi-

vidual pumps

Values: ON, OFF

Factory setting: OFF

5.4.6.0

Max. running time of individual 

pumps

Value range: 0 to 60

Factory setting: 10

5.4.7.0

Behaviour in case of mains con-

nection errors**

Values: OFF, Message, Stop 

Pumps

Factory setting: Stop Pumps

5.4.8.0

Behaviour on activation of ther-

mal motor winding monitoring 

and leakage detection**

Values: Auto Reset, Manu Reset

Factory setting: Auto Reset

5.4.9.0

Behaviour when “External OFF” 

contact is open**

Values: Ext.Off, Alarm

Factory setting: Ext. off

5.5.0.0

Setting for signal outputs

5.5.1.0

Collective run signal (SBM)** 

function

Values: Ready, Run

Factory setting: Run

5.5.2.0

Collective fault signal function**

Values: Fall, Raise

Factory setting: Raise

5.6.0.0

Pump cycling**

Menu 5: Basic switchgear settings

No.

Description

Display

5.6.1.0

General pump cycling

Values: ON, OFF

Factory setting: ON

5.6.2.0

Pump cycling after time interval

Values: ON, OFF

Factory setting: OFF

5.6.3.0

Running time of base-load pump 

until pump cycling

Value range: 0 to 60

Factory setting: 10

5.7.0.0

Pump kick**

5.7.1.0

Switching pump kick on/off

Values: ON, OFF

Factory setting: OFF

5.7.2.0

Interval between pump kicks

Value range: 1 to 336

Factory setting: 12

5.7.4.0

Running time of pump(s) on 

pump kick

Value range: 1 to 30

Factory setting: 5

* The value range is dependent on the sensor 

measuring range.

** See the function description below

6.4.2.  Explanation of individual functions and settings

Menu 5.1.3.0 / GSM

This menu item is only active if the optionally 

available module has been installed in the switch-

gear. Please contact Wilo customer service for 

more information and for retrofi tting.

Menu 5.2.5.0 / Priority when dry run and high 

water signals are present simultaneously

If the system malfunctions, it may happen that 

both signals are present at the same time. In such 

cases, it is necessary to stipulate which signal is 

overriding:

• “Dry Run” Dry-running protection

• 

“High Water”: High water alarm

Menu 5.2.6.0/ Signal detection for level control

The switchgear can be operated for level meas-

urement both with fl oat switches and with a level 

sensor. The following options are available:

• 

“Floater”: Float switch

• 

“Sensor”: Level sensor

If fl oat switches are used, some of the menu 

items will not be available!

Menu 5.4.7.0 / Behaviour in case of mains con-

nection errors**

This function can only be used with a 3~-mains 

connection. With a 1~-mains connection, this 

Summary of Contents for Control SC-L

Page 1: ...otice de montage et de mise en service es Instrucciones de instalaci n y funcionamiento it Istruzioni di montaggio uso e manutenzione pt Manual de Instala o e funcionamento nl Inbouw en bedieningsvoor...

Page 2: ...Fig 2B Fig 2A Fig 1 1 2 3 4 1 2 3 3 4 5 6 6 7 1 2 3 3 4 6 5 7...

Page 3: ...Fig 4 Fig 3 Fig 5 dry run 4 all OFF 3 P1 ON 1 P2 ON 2 high water 5 5 P1 OFF 2 P1 ON 1 P2 ON 3 P2 OFF 4 6 7 8 low water 4 dry run Ext OFF 5 OFF 3 ON 1 2 high water...

Page 4: ...erating modes and operation principle 40 6 2 Menu control and structure 41 6 3 Initial commissioning 41 6 4 Setting the operating parameters 41 6 5 Forced switching of the pumps in case of dry run or...

Page 5: ...ual refers to the switchgear indicated on the title page 1 5 Warranty In general the specifications in the current Gen eral Terms and Conditions apply to the warranty You can find these here www wilo...

Page 6: ...must be shut down immediately by the operator Tools and other objects should be kept in their designated places The switchgear may not be installed in potentially explosive areas There is a risk of e...

Page 7: ...LED indicators The switchgear comprises the following main components Main switch for switching the switchgear on off Control panel LEDs for displaying the current operating state operation fault LC d...

Page 8: ...sion for pumps and signal transmitters used in potentially explosive areas 3 7 Options Connection for 3 or 4 pumps Customer specific adjustments for special appli cations 3 8 Scope of delivery Switchg...

Page 9: ...by a qualified electrician The installation location must be clean dry and free of vibrations Avoid exposing the switchgear to direct sunlight The customer must provide the power supply cables These m...

Page 10: ...using the level sensor the switching point must be set via the menu A forced switch off of the pumps always occurs irrespective of the selected signal transmitter 5 3 5 High water alarm The high water...

Page 11: ...otection be set 5 above the current measured at the duty point Star delta activation Set the motor protection to 0 58 x the rated current The maximum start up time in star connection is 3 seconds Pump...

Page 12: ...2 5 m Display range 0 2 5 m Setting 1 V 0 25 m Insert the cable ends of the cable laid on site through the threaded cable connections and secure accordingly Connect the wires to the terminal strip acc...

Page 13: ...ed Fig 4 Illustration of the switching points with a level sensor in the Empty operating mode using the example of two pumps 1 Base load pump ON 5 Dry running protection 2 Base load pump OFF 6 High wa...

Page 14: ...All terminals must be retightened Motor protection correctly set The separate HAND 0 AUTO switch for each pump must be set to AUTO A The factory setting for these is 0 OFF Switching on 1 Turn main sw...

Page 15: ...2 4 Peak load pump 1 off Value range 0 06 to 12 42 Factory setting 0 50 1 2 2 5 Peak load pump 2 on Value range 0 09 to 12 45 Factory setting 1 00 1 2 2 6 Peak load pump 2 off Value range 0 06 to 12...

Page 16: ...2 2 x Running time of the individual pumps 4 2 3 0 Unit switching cycles 4 2 4 x Switching cycles of the individual pumps 4 3 0 0 Details of switchgear 4 3 1 0 Switchgear type 4 3 2 0 Serial number as...

Page 17: ...6 1 0 General pump cycling Values ON OFF Factory setting ON 5 6 2 0 Pump cycling after time interval Values ON OFF Factory setting OFF 5 6 3 0 Running time of base load pump until pump cycling Value...

Page 18: ...tion Run At least one pump is running Menu 5 5 2 0 SSM The required logic of the collective fault signal can be set Fall negative logic falling edge Rise positive logic rising edge Menu 5 6 0 0 Pump c...

Page 19: ...ide potentially explosive areas 7 3 Activating the switchgear NOTE Following a power supply interruption the switchgear will automatically start up in the last operating mode set 1 Turn main switch to...

Page 20: ...hand the cover must be opened There is a risk of fatal injury due to live parts This work may only be carried out by a qualified electrician In case of a control failing the individual pumps can be sw...

Page 21: ...nsure reliable operation various maintenance tasks must be carried out regularly NOTE When used in sewage lifting units inside build ings or on land plots the maintenance intervals and work shown in D...

Page 22: ...ected pump was tripped Remedy See installation and operating instructions for the connected pump request these from Wilo customer service E20 x Fault Temperature monitor for motor winding Cause Motor...

Page 23: ...r in power supply phase error incorrect rotat ing field low voltage Error in motor winding WSK PTC impermeability External off Pump Pump 1 Pump 2 Pump 3 Pump 4 Pump cycling Time dependent pump cycling...

Page 24: ...d pump 3 Activation threshold Peak load pump Delay time for activation Peak load pump 1 Deactivation threshold Peak load pump 2 Deactivation threshold Peak load pump 3 Deactivation threshold Peak load...

Page 25: ...0 071 24 15 0 0 087 6 15 0 0 063 12 15 0 0 052 18 15 0 0 045 24 18 5 0 059 6 18 5 0 043 12 18 5 0 035 18 22 0 0 046 6 22 0 0 033 12 22 0 0 027 18 11 3 Spare parts Spare parts can be ordered from Wilo...

Page 26: ......

Page 27: ...ot kompatybilno ci elektromagnetycznej 2004 108 WE 2004 108 EG Sm rnice pro n zk nap t 2006 95 ES dyrektyw niskonapi ciow 2006 95 WE 2006 95 EG pou it harmoniza n normy zejm na stosowanymi normami zha...

Page 28: ......

Page 29: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: