44
WILO SE 05/2016 V05 DIN A4
English
OPERATION AND FUNCTION
Menu 5: Basic switchgear settings
No.
Description
Display
5.2.5.0
Priority when dry run and high
water signals are present simul-
taneously**
Values: Dry Run, High Water
Factory setting: Dry Run
5.2.6.0
Signal detection for level con-
trol**
Values: Floater, Sensor
Factory setting: Sensor
5.4.0.0
Limit values
5.4.1.0
Dry run level
Value range*: 0.01 to 12.39
Factory setting: 0.12
5.4.2.0
High water alarm level
Value range*: 0.12 to 12.50
Factory setting: 1.50
5.4.4.0
High water alarm delay
Value range: 0 to 30
Factory setting: 0
5.4.5.0
Running time monitoring of indi-
vidual pumps
Values: ON, OFF
Factory setting: OFF
5.4.6.0
Max. running time of individual
pumps
Value range: 0 to 60
Factory setting: 10
5.4.7.0
Behaviour in case of mains con-
nection errors**
Values: OFF, Message, Stop
Pumps
Factory setting: Stop Pumps
5.4.8.0
Behaviour on activation of ther-
mal motor winding monitoring
and leakage detection**
Values: Auto Reset, Manu Reset
Factory setting: Auto Reset
5.4.9.0
Behaviour when “External OFF”
contact is open**
Values: Ext.Off, Alarm
Factory setting: Ext. off
5.5.0.0
Setting for signal outputs
5.5.1.0
Collective run signal (SBM)**
function
Values: Ready, Run
Factory setting: Run
5.5.2.0
Collective fault signal function**
Values: Fall, Raise
Factory setting: Raise
5.6.0.0
Pump cycling**
Menu 5: Basic switchgear settings
No.
Description
Display
5.6.1.0
General pump cycling
Values: ON, OFF
Factory setting: ON
5.6.2.0
Pump cycling after time interval
Values: ON, OFF
Factory setting: OFF
5.6.3.0
Running time of base-load pump
until pump cycling
Value range: 0 to 60
Factory setting: 10
5.7.0.0
Pump kick**
5.7.1.0
Switching pump kick on/off
Values: ON, OFF
Factory setting: OFF
5.7.2.0
Interval between pump kicks
Value range: 1 to 336
Factory setting: 12
5.7.4.0
Running time of pump(s) on
pump kick
Value range: 1 to 30
Factory setting: 5
* The value range is dependent on the sensor
measuring range.
** See the function description below
6.4.2. Explanation of individual functions and settings
Menu 5.1.3.0 / GSM
This menu item is only active if the optionally
available module has been installed in the switch-
gear. Please contact Wilo customer service for
more information and for retrofi tting.
Menu 5.2.5.0 / Priority when dry run and high
water signals are present simultaneously
If the system malfunctions, it may happen that
both signals are present at the same time. In such
cases, it is necessary to stipulate which signal is
overriding:
• “Dry Run” Dry-running protection
•
“High Water”: High water alarm
Menu 5.2.6.0/ Signal detection for level control
The switchgear can be operated for level meas-
urement both with fl oat switches and with a level
sensor. The following options are available:
•
“Floater”: Float switch
•
“Sensor”: Level sensor
If fl oat switches are used, some of the menu
items will not be available!
Menu 5.4.7.0 / Behaviour in case of mains con-
nection errors**
This function can only be used with a 3~-mains
connection. With a 1~-mains connection, this