Installation and operating instructions Wilo-Control SC-L 41

OPERATION AND FUNCTION English

NOTE

In case of level measurement using a level 

sensor, forced switch-on or switch-off only 

takes place if dry-running protection and the 

high water alarm are additionally realised with a 

fl oat switch!

6.2.  Menu control and structure

6.2.1.  Control

Fig. 6: Operation

The menu is controlled via the operating knob:

• 

Turn: Selection and set values

• 

Press: Change menu level or confi rm value

6.2.2.  Set-up

The menu is divided into two areas:

• Easy menu

For quick commissioning using the factory set-

tings, only the operating mode and the activation 

and deactivation values need to be set here.

• Expert menu

For display and setting of all parameters.

Open menu

1.  Press operating knob for 3 seconds.

2.  Menu item 1.0.0.0 appears.

3. 

Turn operating knob to left: Easy menu

Turn operating knob to right: Expert menu

6.3.  Initial commissioning

NOTE

Observe the installation and operating in-

structions for products provided on-site (fl oat 

switches, level sensors, connected consumers) 

as well as the system documentation!

The following points must be checked before the 

initial start-up:

• Check the installation.

• All terminals must be retightened.

• Motor protection correctly set.

• The separate HAND-0-AUTO switch for each 

pump must be set to “AUTO (A)”. The factory 

setting for these is “0 (OFF)”!

Switching on

1.  Turn main switch to ON position.

2.  The display lights up and outputs the latest 

information. The display appearance changes 

depending on the signal transmitter connected:

3.  The “Standby” symbol appears and the switch-

gear is ready for operation. You can now set the 

individual operating parameters.

NOTE

If the red fault LED lights up or fl ashes imme-

diately after activation, observe the error code 

information on the display!

Fig. 7: 

Appearance of display with fl oat switch

1

2

3

4

5

1 Control with standby pump
2

Current pump status: Number of registered pumps/

pump on/pump off

3

Switching state of the individual fl oat switches

4 Float switch designation
5 Area for the display of graphical symbols

Fig. 8: Appearance of display with level sensor

1

2

3

4

5

1 Control with standby pump
2

Current pump status: Number of registered pumps/

pump on/pump off

3

Current fi ll level

4 Unit of value currently displayed
5 Area for the display of graphical symbols

6.4.  Setting the operating parameters

The menu is divided into seven areas:

1.  Control parameters (operating mode, start/stop 

delays)

2. 

Communication parameters (fi eld bus)

3.  Pump activation (activation and deactivation of 

the connected pumps)

Summary of Contents for Control SC-L

Page 1: ...otice de montage et de mise en service es Instrucciones de instalaci n y funcionamiento it Istruzioni di montaggio uso e manutenzione pt Manual de Instala o e funcionamento nl Inbouw en bedieningsvoor...

Page 2: ...Fig 2B Fig 2A Fig 1 1 2 3 4 1 2 3 3 4 5 6 6 7 1 2 3 3 4 6 5 7...

Page 3: ...Fig 4 Fig 3 Fig 5 dry run 4 all OFF 3 P1 ON 1 P2 ON 2 high water 5 5 P1 OFF 2 P1 ON 1 P2 ON 3 P2 OFF 4 6 7 8 low water 4 dry run Ext OFF 5 OFF 3 ON 1 2 high water...

Page 4: ...erating modes and operation principle 40 6 2 Menu control and structure 41 6 3 Initial commissioning 41 6 4 Setting the operating parameters 41 6 5 Forced switching of the pumps in case of dry run or...

Page 5: ...ual refers to the switchgear indicated on the title page 1 5 Warranty In general the specifications in the current Gen eral Terms and Conditions apply to the warranty You can find these here www wilo...

Page 6: ...must be shut down immediately by the operator Tools and other objects should be kept in their designated places The switchgear may not be installed in potentially explosive areas There is a risk of e...

Page 7: ...LED indicators The switchgear comprises the following main components Main switch for switching the switchgear on off Control panel LEDs for displaying the current operating state operation fault LC d...

Page 8: ...sion for pumps and signal transmitters used in potentially explosive areas 3 7 Options Connection for 3 or 4 pumps Customer specific adjustments for special appli cations 3 8 Scope of delivery Switchg...

Page 9: ...by a qualified electrician The installation location must be clean dry and free of vibrations Avoid exposing the switchgear to direct sunlight The customer must provide the power supply cables These m...

Page 10: ...using the level sensor the switching point must be set via the menu A forced switch off of the pumps always occurs irrespective of the selected signal transmitter 5 3 5 High water alarm The high water...

Page 11: ...otection be set 5 above the current measured at the duty point Star delta activation Set the motor protection to 0 58 x the rated current The maximum start up time in star connection is 3 seconds Pump...

Page 12: ...2 5 m Display range 0 2 5 m Setting 1 V 0 25 m Insert the cable ends of the cable laid on site through the threaded cable connections and secure accordingly Connect the wires to the terminal strip acc...

Page 13: ...ed Fig 4 Illustration of the switching points with a level sensor in the Empty operating mode using the example of two pumps 1 Base load pump ON 5 Dry running protection 2 Base load pump OFF 6 High wa...

Page 14: ...All terminals must be retightened Motor protection correctly set The separate HAND 0 AUTO switch for each pump must be set to AUTO A The factory setting for these is 0 OFF Switching on 1 Turn main sw...

Page 15: ...2 4 Peak load pump 1 off Value range 0 06 to 12 42 Factory setting 0 50 1 2 2 5 Peak load pump 2 on Value range 0 09 to 12 45 Factory setting 1 00 1 2 2 6 Peak load pump 2 off Value range 0 06 to 12...

Page 16: ...2 2 x Running time of the individual pumps 4 2 3 0 Unit switching cycles 4 2 4 x Switching cycles of the individual pumps 4 3 0 0 Details of switchgear 4 3 1 0 Switchgear type 4 3 2 0 Serial number as...

Page 17: ...6 1 0 General pump cycling Values ON OFF Factory setting ON 5 6 2 0 Pump cycling after time interval Values ON OFF Factory setting OFF 5 6 3 0 Running time of base load pump until pump cycling Value...

Page 18: ...tion Run At least one pump is running Menu 5 5 2 0 SSM The required logic of the collective fault signal can be set Fall negative logic falling edge Rise positive logic rising edge Menu 5 6 0 0 Pump c...

Page 19: ...ide potentially explosive areas 7 3 Activating the switchgear NOTE Following a power supply interruption the switchgear will automatically start up in the last operating mode set 1 Turn main switch to...

Page 20: ...hand the cover must be opened There is a risk of fatal injury due to live parts This work may only be carried out by a qualified electrician In case of a control failing the individual pumps can be sw...

Page 21: ...nsure reliable operation various maintenance tasks must be carried out regularly NOTE When used in sewage lifting units inside build ings or on land plots the maintenance intervals and work shown in D...

Page 22: ...ected pump was tripped Remedy See installation and operating instructions for the connected pump request these from Wilo customer service E20 x Fault Temperature monitor for motor winding Cause Motor...

Page 23: ...r in power supply phase error incorrect rotat ing field low voltage Error in motor winding WSK PTC impermeability External off Pump Pump 1 Pump 2 Pump 3 Pump 4 Pump cycling Time dependent pump cycling...

Page 24: ...d pump 3 Activation threshold Peak load pump Delay time for activation Peak load pump 1 Deactivation threshold Peak load pump 2 Deactivation threshold Peak load pump 3 Deactivation threshold Peak load...

Page 25: ...0 071 24 15 0 0 087 6 15 0 0 063 12 15 0 0 052 18 15 0 0 045 24 18 5 0 059 6 18 5 0 043 12 18 5 0 035 18 22 0 0 046 6 22 0 0 033 12 22 0 0 027 18 11 3 Spare parts Spare parts can be ordered from Wilo...

Page 26: ......

Page 27: ...ot kompatybilno ci elektromagnetycznej 2004 108 WE 2004 108 EG Sm rnice pro n zk nap t 2006 95 ES dyrektyw niskonapi ciow 2006 95 WE 2006 95 EG pou it harmoniza n normy zejm na stosowanymi normami zha...

Page 28: ......

Page 29: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: