English INSTALLATION

Fig. 2: Overview of individual components 

A Switchgear for direct starting

B Switchgear for star-delta activation
1 Switchgear main switch 5 Fuse protection of 

pumps

2 Main printed circuit 

board

6

Contactor combina-

tions including motor 

protection

3 Terminal strip

7 HAND-0-AUTO- switch 

for each pump

4 Earthing rod

5.4.1.  Switchgear mains connection

Insert the cable ends of the power supply cable 

laid on-site through the threaded cable connec-

tions and secure them accordingly.

Connect the wires to the terminal strip according 

to the wiring diagram.

The protective earth conductor (PE) is connected 

to the ground rod.

• 

Mains connection 1~230 V:

• 

Cable: 3-core

• 

Wire: L, N, PE

• 

Mains connection 3~400 V:

• 

Cable: 4-core

• 

Wire: L1, L2, L3, PE

• A 

clockwise

 rotating field must be present!

5.4.2.  Pumps mains connection

Insert the cable ends of the pump power supply 

cable laid on-site through the threaded cable 

connections and secure accordingly.

Connect the wires to the terminal strip according 

to the wiring diagram.

The protective earth conductor (PE) is connected 

to the ground rod.

• 

Direct activation 1~230 V:

• 

Wire: L, N, PE

• 

Direct activation 3~400 V:

• 

Wire: U, V, W, PE

• A 

clockwise

 rotating field must be present!

• 

Star-delta activation:

• 

Wire: U1, V1, W1, U2, V2, W2, PE

• A 

clockwise

 rotating field must be present!

After the pumps have been connected correctly, 

the motor protection needs to be adjusted and 

the pump enabled.

Adjusting the motor protection

The max. permissible motor current must be set 

directly on the overload relay.

• Direct activation

At full load, the motor protection should be set to 

the rated current shown on the rating plate.

At partial load, we recommend that the motor 

protection be set 5% above the current measured 

at the duty point.

• Star-delta activation

Set the motor protection to 0.58 x the rated 

current.

The maximum start-up time in star connection is 

3 seconds.

Pumps enabled

Set the separate HAND-0-AUTO switch to “AUTO 

(A)” in the switch cabinet for each pump. This is 

factory-set to the position “0 (OFF)” .

5.4.3.  Winding temperature monitoring connection

Bimetal or PTC sensors can be connected to each 

connected pump for temperature monitoring.

Connect the wires to the terminal strip according 

to the wiring diagram.

NOTE 

No external voltage may be applied!

5.4.4.  Leakage detection connection

A moisture probe can be connected to each con-

nected pump for leakage detection. The threshold 

value is fixed in the switchgear.

Connect the wires to the terminal strip according 

to the wiring diagram.

NOTE 

No external voltage may be applied!

5.4.5.  Connection for level measurement signal trans-

mitter

Level measurement can be performed via three 

float switches or a level sensor. Connection of 

electrodes is not possible!

Insert the cable ends of the cable laid on-site 

through the threaded cable connections and 

secure accordingly.

Connect the wires to the terminal strip according 

to the wiring diagram.

NOTE

•  No external voltage may be applied!
•  A max. of 2 pumps can be actuated with level 

measurement using a float switch.

•  A max. of 4 pumps can be actuated with level 

measurement using a level sensor.

5.4.6.  Connection of dry-running protection using a 

separate float switch

Dry-running protection can be realised using a 

float switch via a potential-free contact. The 

terminals are fitted with a converter bridge in the 

factory.

Insert the cable ends of the cable laid on-site 

through the threaded cable connections and 

secure accordingly.

Remove the converter bridge and connect the 

wires to the terminal strip according to the wiring 

diagram.

• 

Contact:

• 

Connected: No dry run

• 

Open: Dry run

Summary of Contents for Control SC-L

Page 1: ...otice de montage et de mise en service es Instrucciones de instalaci n y funcionamiento it Istruzioni di montaggio uso e manutenzione pt Manual de Instala o e funcionamento nl Inbouw en bedieningsvoor...

Page 2: ...Fig 2B Fig 2A Fig 1 1 2 3 4 1 2 3 3 4 5 6 6 7 1 2 3 3 4 6 5 7...

Page 3: ...Fig 4 Fig 3 Fig 5 dry run 4 all OFF 3 P1 ON 1 P2 ON 2 high water 5 5 P1 OFF 2 P1 ON 1 P2 ON 3 P2 OFF 4 6 7 8 low water 4 dry run Ext OFF 5 OFF 3 ON 1 2 high water...

Page 4: ...erating modes and operation principle 40 6 2 Menu control and structure 41 6 3 Initial commissioning 41 6 4 Setting the operating parameters 41 6 5 Forced switching of the pumps in case of dry run or...

Page 5: ...ual refers to the switchgear indicated on the title page 1 5 Warranty In general the specifications in the current Gen eral Terms and Conditions apply to the warranty You can find these here www wilo...

Page 6: ...must be shut down immediately by the operator Tools and other objects should be kept in their designated places The switchgear may not be installed in potentially explosive areas There is a risk of e...

Page 7: ...LED indicators The switchgear comprises the following main components Main switch for switching the switchgear on off Control panel LEDs for displaying the current operating state operation fault LC d...

Page 8: ...sion for pumps and signal transmitters used in potentially explosive areas 3 7 Options Connection for 3 or 4 pumps Customer specific adjustments for special appli cations 3 8 Scope of delivery Switchg...

Page 9: ...by a qualified electrician The installation location must be clean dry and free of vibrations Avoid exposing the switchgear to direct sunlight The customer must provide the power supply cables These m...

Page 10: ...using the level sensor the switching point must be set via the menu A forced switch off of the pumps always occurs irrespective of the selected signal transmitter 5 3 5 High water alarm The high water...

Page 11: ...otection be set 5 above the current measured at the duty point Star delta activation Set the motor protection to 0 58 x the rated current The maximum start up time in star connection is 3 seconds Pump...

Page 12: ...2 5 m Display range 0 2 5 m Setting 1 V 0 25 m Insert the cable ends of the cable laid on site through the threaded cable connections and secure accordingly Connect the wires to the terminal strip acc...

Page 13: ...ed Fig 4 Illustration of the switching points with a level sensor in the Empty operating mode using the example of two pumps 1 Base load pump ON 5 Dry running protection 2 Base load pump OFF 6 High wa...

Page 14: ...All terminals must be retightened Motor protection correctly set The separate HAND 0 AUTO switch for each pump must be set to AUTO A The factory setting for these is 0 OFF Switching on 1 Turn main sw...

Page 15: ...2 4 Peak load pump 1 off Value range 0 06 to 12 42 Factory setting 0 50 1 2 2 5 Peak load pump 2 on Value range 0 09 to 12 45 Factory setting 1 00 1 2 2 6 Peak load pump 2 off Value range 0 06 to 12...

Page 16: ...2 2 x Running time of the individual pumps 4 2 3 0 Unit switching cycles 4 2 4 x Switching cycles of the individual pumps 4 3 0 0 Details of switchgear 4 3 1 0 Switchgear type 4 3 2 0 Serial number as...

Page 17: ...6 1 0 General pump cycling Values ON OFF Factory setting ON 5 6 2 0 Pump cycling after time interval Values ON OFF Factory setting OFF 5 6 3 0 Running time of base load pump until pump cycling Value...

Page 18: ...tion Run At least one pump is running Menu 5 5 2 0 SSM The required logic of the collective fault signal can be set Fall negative logic falling edge Rise positive logic rising edge Menu 5 6 0 0 Pump c...

Page 19: ...ide potentially explosive areas 7 3 Activating the switchgear NOTE Following a power supply interruption the switchgear will automatically start up in the last operating mode set 1 Turn main switch to...

Page 20: ...hand the cover must be opened There is a risk of fatal injury due to live parts This work may only be carried out by a qualified electrician In case of a control failing the individual pumps can be sw...

Page 21: ...nsure reliable operation various maintenance tasks must be carried out regularly NOTE When used in sewage lifting units inside build ings or on land plots the maintenance intervals and work shown in D...

Page 22: ...ected pump was tripped Remedy See installation and operating instructions for the connected pump request these from Wilo customer service E20 x Fault Temperature monitor for motor winding Cause Motor...

Page 23: ...r in power supply phase error incorrect rotat ing field low voltage Error in motor winding WSK PTC impermeability External off Pump Pump 1 Pump 2 Pump 3 Pump 4 Pump cycling Time dependent pump cycling...

Page 24: ...d pump 3 Activation threshold Peak load pump Delay time for activation Peak load pump 1 Deactivation threshold Peak load pump 2 Deactivation threshold Peak load pump 3 Deactivation threshold Peak load...

Page 25: ...0 071 24 15 0 0 087 6 15 0 0 063 12 15 0 0 052 18 15 0 0 045 24 18 5 0 059 6 18 5 0 043 12 18 5 0 035 18 22 0 0 046 6 22 0 0 033 12 22 0 0 027 18 11 3 Spare parts Spare parts can be ordered from Wilo...

Page 26: ......

Page 27: ...ot kompatybilno ci elektromagnetycznej 2004 108 WE 2004 108 EG Sm rnice pro n zk nap t 2006 95 ES dyrektyw niskonapi ciow 2006 95 WE 2006 95 EG pou it harmoniza n normy zejm na stosowanymi normami zha...

Page 28: ......

Page 29: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...