PAGE 74 OF 102
INFLEXION PLUS
OPERATING INSTRUCTIONS
TP-5211901-C
JUNE 2021
The cable used to connect the Sensor unit to the positioner should be connected to the bottom of
the Sensor unit and wired into the base PC board. Consult The Will-Burt Company’s engineering
for electrically connecting the D-TEC® Sensor.
8.2.2
D-TEC® Functionality
The optional D-TEC® Sensor provides additional limited protection against raising the mast into
power lines. On Night Scan fold-down units, as soon as the mast begins tilting, the control begins
initiating the D-TEC® Sensor and self-tests it until it either passes, or the mast reaches the point
where the RCP becomes active (at 90°). Assuming that it passes, the operator is then permitted
to extend the mast. For vertical mast applications, the self-test is performed during power up and
the unit begins actively sensing. If the mast senses an electrical field strength above the alarm
threshold, the mast will stop extending even though the operator continues to push the "Mast Up"
button. In this case, there will be a message displayed on the alphanumeric display of the
Remote Control(s) (for Night Scan models). If the operator believes the sensed condition to be
false, they may clear it in either of two ways: momentarily initiating an Auto Stow® function, or
lowering the mast to the bottom of the 90° position (for fold-down models). This will clear the
alarm and allow the operator another chance to raise the mast to its full extension. The following
messages may be displayed on the Remote Control(s).
The following table contains possible D-TEC® messages:
Table 8-1 D-TEC® Messages
Message
Meaning
Root Issue
D-TEC® Testing
The D-TEC®
Sensor is
performing a self-
test.
The D-TEC® has repeatedly been trying to pass
the self-test while moving to the RCP active
position. Normally, it will pass one of these
attempts and no message will be displayed. If not,
once there it tries one more time to pass and this
message will displayed during the self-test.
Power Line E-Field The D-TEC® has
sensed voltage
from a power line.
A power line may be in close proximity. If so, move
the vehicle to a location away from the power line,
and then redeploy the system.
Power Line H-Field The D-TEC® has
sensed current
from a power line.
A power line may be in close proximity. If so, move
the vehicle to a location away from the power line,
and then redeploy the system.
D-TEC OSHA Limit The D-TEC® has
sensed voltage
from a very high
power line.
A power line may be in close proximity. If so, move
the vehicle to a location away from the power line,
and then redeploy the system.
Summary of Contents for Inflexion Plus 1.8
Page 2: ......
Page 6: ...PAGE 4 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 16: ...PAGE 14 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 30: ...PAGE 28 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 50: ...PAGE 48 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 62: ...PAGE 60 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 80: ...PAGE 78 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 81: ...PAGE 79 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 82: ...PAGE 80 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 94: ...PAGE 92 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 96: ...PAGE 94 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...
Page 100: ...PAGE 98 OF 102 INFLEXION PLUS OPERATING INSTRUCTIONS TP 5211901 C JUNE 2021 ...