EN
14235429.01 01/2018 EN/DE/FR/ES
16
WIKA operating instructions models RLS
Connection with capacitive load
To increase the service life of the contacts, we recommend
operation with a contact protection relay.
Connection diagrams, see product label
5.4 Commissioning
Switch on the voltage supply of the connected control device. Fill the
vessel and the check the switch points of the float switch for function.
WARNING!
Ensure that the functional check does not start any
unintended processes.
Always observe the mounting and operating instructions of accessories
when commissioning them.
R
S
= 220 Ω (for AC 230 V)
C₁ = internal capacitance
S1
R
S
+
–
C
1
AC 230 V
AC voltage current limitation
e.g. for electronic time relay
Relay
R
S
= 22 Ω (47 Ω for contacts ≤ 10 VA)
C₁ = internal capacitance
S1
R
S
+
–
C
1
DC 24 V
Current limitation, DC voltage
e.g. for PLC, PCS and cables > 50 m
PLC
5. Commissioning, operation