13
5.3
Electrical connection
■
The electrical connection must only be made by qualified skilled
personnel.
■
Connection details and switching functions are given on the
connection diagram. Connection terminals are appropriately marked.
■
Seal the cable bushing
at the connection housing
(see
illustration in chapter 5.2 “Mounting”).
■
The mains connection lines to be provided must be dimensioned
for maximum instrument current supply and comply with IEC 227 or
IEC 245.
WARNING!
Electrical connection errors of the float switches can destroy
the reed contacts. This can lead to a malfunction in the plant
and thus lead to injury to personnel or damage to equipment.
▶
No direct operation in circuits with inductive loads.
▶
No direct operation in circuits with capacitive loads, e.g.
PLC, PCS or cable lengths > 50 m.
▶
Do not exceed the permissible switching power.
DANGER!
Physical injuries
With float switches with connection cable without protective
conductor connection, it is possible for the switch to become
live in the event of a malfunction. Any contact can result in
physical or even fatal injury.
▶
Only operate these switches at safety extra-low voltage
in accordance with VDE0100 or fit them so that the float
switch is electrically connected to the equipotential
bonding.
5. Commissioning, operation
Summary of Contents for RLS-1000
Page 24: ...EN 14235429 01 01 2018 EN DE FR ES 24 WIKA operating instructions models RLS...
Page 46: ...DE 14235429 01 01 2018 EN DE FR ES 46 WIKA Betriebsanleitung Typen RLS...
Page 68: ...FR 14235429 01 01 2018 EN DE FR ES 68 WIKA mode d emploi types RLS...
Page 90: ...14235429 01 01 2018 EN DE FR ES 90 WIKA operating instructions models RLS...
Page 91: ...WIKA operating instructions models RLS 14235429 01 01 2018 EN DE FR ES 91...